Publication 1734-UM011C-EN-P - January 2006
C-6        1734 POINT I/O Module/RSLogix 5000 Controller Tag Reference
Digital 2 POINT Output – 
With Over Load and Open 
Load Diagnostic Status
1734-OB2E
2 POINT 10V…28V dc Electronically Fused Output, Source
1734-OB2EP
2 POINT 10V…28V dc Electronically Fused Protected Output, Source
Configuration Data
Data Type
Default
Value
Valid Data Values
Fault Mode - POINT 0, 1
SINT, BIT
0
0=Fault Value
1=Hold Last State
Fault Value - POINT 0, 1
SINT, BIT
0
0=Off
1=On
Program Mode - POINT 0, 1
SINT, BIT
0
0=Program Value
1=Hold Last State
Program Value - POINT 0, 1
SINT, BIT
0
0=Off
1=On
No Load Enable - POINT 0, 1
(Wire Off Diagnostic)
SINT, BIT
1
0=Disabled
1=Enabled
Auto Restart Enable - POINT 0, 1
(Over Load Behavior)
SINT, BIT
0
0=Latch Off
1=Auto Retry
Fault Latch Enable - POINT 0, 1
(Open Load or Over Load)
SINT, BIT
0
0=No Latching
1=Alarms Latch
Input Data
Data Type
Default
Value
Valid Data Values
Status Data - POINT 0, 1
(Open Load or Over Load)
SINT, BIT
0
0=Off
1=On (Load Fault)
Output Data
Data Type
Default
Value
Valid Data Values
Output Data - POINT 0, 1
SINT, BIT
0
0=Off
1=On