C-18        1734 POINT I/O Module/RSLogix 5000 Controller Tag Reference
1734-IT2
2 Channel Thermocouple Input, Isol.
Configuration Data
Data Type
Default
Value
Valid Data Values
Temperature Mode Channel 1
SINT
1
0=mV/Custom Scale
1=°C
2=°F
3=°K
4=°R
Cold Junction Enable Channel 1
SINT
1
0=Disabled
1=Enabled
Cold Junction Offset Channel 1
INT
0
0…7,000 (0.00…70.00)
Input Data
Data Type
Default
Value
Valid Data Values
Data Channel 0
INT
0
-32,768…32,767
Data Channel 1
INT
0
-32,768…32,767
Status Byte Channel 0
SINT
0
Bit 0 Fault
Bit 1 Calibration
Bit 2 LowAlarm
Bit 3 HighAlarm
Bit 4 LowLowAlarm
Bit 5 HighHighAlarm
Bit 6 Underrange
Bit 7 Overrange
Status Byte Channel 1
SINT
0
Bit 0 Fault
Bit 1 Calibration
Bit 2 LowAlarm
Bit 3 HighAlarm
Bit 4 LowLowAlarm
Bit 5 HighHighAlarm
Bit 6 Underrange
Bit 7 Overrange
Cold Junction Data
INT
0
-32,768…32,767
Output Data
Data Type
Default
Value
Valid Data Values
None