About the Adapter        1-7
Support of Rack-optimized 
and Direct Connections
The 1734-AENT adapter supports both direct and rack-optimized 
connections. A direct connection is a real-time data transfer link 
between the controller and whatever module occupies the slot that 
the configuration data references. Direct connection messaging occurs 
at a cyclic rate specified by the RPI during configuration. A 
rack-optimized connection is a grouping of data from more than one 
I/O module into a single block of data sent over a single connection 
at the same data rate. 
Rack-optimized connections reduce the total number of connections 
needed to transfer data when using many I/O modules in a system. 
The following example illustrates the benefit of rack-optimized 
connections.
Assume you set up a system that contains 8 digital I/O modules 
interfaced to a 1734-AENT adapter. If you use direct connections to 
transfer data to each of the these I/O modules, you need 8 
connections to transfer all of the data, one to each of the 8 I/O 
modules. If you use a rack-optimized connection to transfer the data, 
you only need a single connection – the connection to the 1734-AENT 
adapter.
See the EtherNet/IP Performance and Application Guide, publication 
number ENET-AP001, for more information on connections.
Mix Rack-optimized and Direct Connections
You can mix communication formats for different I/O modules 
communicating through the same adapter. I/O modules set up to use 
rack optimization communicate at the rate of the RPI configured for 
the 1734-AENT adapter. I/O modules configured for direct 
communication communicate at their own set RPIs and ignore the 
1734-AENT adapter’s RPI.
IMPORTANT
Although rack-optimized connections offer an 
efficient way to use resources, there are a few 
limitations on their use:
• You can use only rack-optimized connections 
to send data to and from digital I/O modules. 
Analog or speciality I/O requires direct 
connections.
• All data is sent at the same time as the RPI rate 
of the 1734-AENT adapter.