Schneider Electric 66846 Manual De Usuario

Descargar
Página de 81
 
Network  
 
 
 
Management Card 
User Manual 
 
 
 
Network Management Card
 – User Manual 
34003676EN/HA
 
Page 
48/81
 
 
 
This page is used to define either the shutdown or the notification settings used by the Network Shutdown 
Modules that connect to Network Management Card. These settings are used by the Network Shutdown 
Modules if they are in centralized-configuration mode or if their configuration is not valid. 
 
 
Shutdown After (time before shutdown) This is the time in seconds that the system waits following 
failure of AC power before initiating the system-shutdown procedure. This value must be selected to 
provide users with enough time to close their applications and disconnect, but within the battery backup 
time provided by the UPS. 
 If another criterion occurs before the end of the shutdown timer, the shutdown procedure is immediately 
run.  
This parameter is optional, uncheck it to invalidate 
 
Shutdown Duration : This is the time in seconds required by the system to go through its shutdown 
procedure. 
 
Broadcast : Send network notifications to the Administrators and Users groups on events 
 
If you wish to set up a new configuration for the Network Shutdown Modules already set to centralized-
configuration mode, proceed as indicated below.  
 
Change the Network Shutdown Module parameters in the page “Central Shutdown Configuration”.  
 
Click the Save button. Open the List of notified applications. 
Select the Network Shutdown Modules to receive the new configuration. 
Press the button “Remove”  They reconnect and use the new configuration 
3.5.5  STS Notified Applications 
Click the “Notified Application” section in the menu. 
 
Security: 
the administrator has to enter his login/password to view this information.  
 
This menu enables:  
 
The addition of the supervision stations receiving traps and configuration of the trap type. 
 
To list all the Notified Applications and the main parameters. 
 
Simulate events to test notification and shutdown of the Notified Applications. 
Up to 50 destinations can be managed by the card.