list. Connection is made with the server and the date and time are set after clicking on the “Save” button. 
Time is updated every hour. 
The card uses the NTP protocol (UDP 123 port) and the firewall must be set accordingly, no error message 
is generated if the time server contact fails  
 
Daylight Saving Time: Enables corrections due to summer / winter time changes, this option must be 
supported by the NTP server. 
 
Note 1: 
Time drift is related to card electronics. It may be up to a maximum of +/- 2min/month. 
 
3.6  Environment 
The environment sensor is an option that enables temperature and humidity to be measured, and indication of 
the position of two external contacts. It is connected with a standard network cable to the Card Settings port of 
the Network Management Card. 
On startup, the card automatically detects sensor presence. The main menu then displays an additional section 
“Environment” with the following elements: 
 
Status 
 
Configuration 
 
Log 
 
Note 1 This function is only accessible with the DA version software (or superior) for the card. This software 
can be downloaded on the 
www.apc.com
 site, from the 
download
 section. 
 
Note 2: To switch the serial port to the configuration mode, just disconnect the sensor cable and reinitialise the 
card by pressing “Reset”. The reverse operation must be performed to manage the environment sensor once 
again. 
 
3.6.1  Characteristics 
 
Temperature measurement from 0 to 70 °C with +/- 1° C accuracy 
 
Humidity measurement from 0 to 100 % with +/- 6 % accuracy 
 
Min. / max. time-stamped function for temperature and humidity  
 
Choice of displaying temperature in Celsius or Fahrenheit 
 
High and low thresholds, hysteresis and offset adjustment via Web interface  
 
Possibility of notification of status changes by e-mail, SMS or SNMP trap 
 
Position detection of 2 dry contacts (maximum sensor/contact distance: 20m)