4.2   The different server and UPS shutdown sequences  
4.2.1  Extended power outage, shutdown initiated by the Shutdown Timer 
During battery backup time, the Shutdown Timer of the Network Management Card is reached: after a user-
defined backup time period, the shutdown of all servers is initiated, followed by the UPS shutdown (depending 
on its configuration). The UPS restarts when utility power is restored (depending on its configuration). 
 
Shutdown Duration: Maximum value of shutdown times of the Network Shutdown Modules subscribed to 
the card and depending on the main UPS output. This value is updated each time a client subscribes/ 
unsubscribes. 
Note: During battery operation, these values are not updated. 
 
Shuts down after the ShutDown Timer + Shutdown Duration after having stopped the servers 
Restarts when utility power is restored (possibility of programming a restart delay) 
 
Utility 
ON 
OFF 
ON 
 
Trap 17 
Trap,11, Trap 29 
ShutdownTim
er 
 
Trap 18 
 
Trap 31  Shutdown 
Duration 
 
 
 
Trap 32 
 
 
NSM  
 
Shutdown   
Reboot 
 
 
UPS output 
 
OFF