1.7 Technical data
1.7.1 Configuration
The user can configure the card with one of the following means:
◗
Web browser
◗
Local serial link
◗
Telnet console
◗
BOOTP/DHCP
◗
Mupgrade
1.7.2 Administration
◗
Up to 50 workstations protected
◗
Up to 15 browsers connected at the same time
◗
E-mail sending configurable according to UPS alarms and transmission of a periodical report
◗
Measurement of temperature and humidity, adjustable thresholds, possibility of sending e-mails and shutting
down the installation
◗
Control of UPS on/off switching via the HTML interface
◗
Adjustment and control Power via the HTML interface, sequential starting of the installation and
optimisation of backup time by shutting down non-priority systems
◗
Adjustment of date and time via NTP server - Daylight Saving Time management
◗
Protection by encrypted password.
◗
Protection by secured connection SSL and SSH
◗
Saving of logs in the non-volatile memory
◗
Automatic language detection according to browser configuration.
◗
Languages available: English / French / Spanish / German / Italian
◗
On-line help available for each page
◗
Card firmware updated via the network
◗
Card configuration deployment on your installed base through network utility (Mupgrade)
1.7.3 Network
◗
Fast ETHERNET 10/100 Mbits compatibility with auto-negotiation on the RJ45 outlet
◗
SNMP trap port modifiable (by default = 162)
1.7.4 MIB (Management Information Base)
◗
MIB IETF UPS (RFC1628) for UPS
◗
MIB MGE V1.7 AD, for UPS
◗
MIB MGE V2.2 AA, for STS
1.7.5 Environment sensor
◗
Temperature measurement from 0 to 70 °C with +/- 1° C accuracy
◗
Measurement of humidity from 0 to 100 % with +/- 6 % accuracy
◗
Min / max time-stamped function for temperature and humidity
◗
Choice of temperature readings in Celsius or Fahrenheit
◗
High and low thresholds, hysteresis and offset adjustable via Web interface