CU111 Specifications
1.Overview
Connecting the RS232C/RS485 multi-drop adapter (CU111) to the T1’s programmer port, you
can use the RS485 computer link function.
By this function, long-distance and one -to- N communications become available.
2.Specifications
(1)Function specification
Item
Specification
Connection
RS232C
 DIN - 8pin (T1 programmer port connector)
RS485
 Removable terminal block 6pin
Length of T1 connection cable  30cm
Status LEDs
 3 (Refer to the following table)
Isolation
 Non isolation between RS232C and RS485
Power Supply
 5Vdc from T1 main unit
Current consumption
 75mA
Size
 30mm(W) 
×
 90mm(H) 
×
 75mm(D) (except cable)
(2)Transmission specification
Item
Specification
Interface
 Conforms to RS232C (T1 side)
 Conforms to RS485  (Host side)
Transmission distance
 30cm (between T1 and adapter)
 Max. 1km (RS485 )
Transmission speed
 9600 bps
Framing
 Start bit    1bit (Fixed)
 Dta bit     8bits (Fixed)
 Parity      Odd parity/ Non (automatic detection)
 Stop bit    1bit (Fixed)
Number of stations
 Max. 32
(3)RS485 transmission cable
Shieled twisted cable which conforms to the RS485, should be used for communication
cable. It’s recommended that 0.9mm diameter or more, 3 pairs or more cables are used.
(4)Operation Status LEDs
Name
Direction
LED Status
(color)
Lit
Not Lit
POWER
(green)
5V power is normal and
connected to T1
5V power is not normal.
RXD
(green)
Host 
 T1
Data receiving
(RXD = 0)
Data not receiving
(RXD = 1)
TXD
(green)
T1 
 Host
Data transmitting
(TXD = 0)
Data not transmitting
(TXD = 1)