Toshiba XLTR-200 Manual De Usuario
59
13.6.2 Supported Subpoints
This application contains a predefined set of FLN subpoints (refer to Table 4).
These points are static for this application, and cannot be edited.
These points are static for this application, and cannot be edited.
Table 4: Supported Subpoints
Point #
Point
Type
Subpoint
Name
Factory
Default
Units
Slope Intercept
On
Text
Off
Text
01 LAO
ADDRESS
99
–
1
0
–
–
02 LAO APPLICATION 2750 –
1
0
–
–
03 LAI FREQ
OUTPUT
0
HZ 0.01
0
–
–
04 LAI OUTPUT
CUR
0
A 0.01
0
–
–
05 LAI OUTPUT
VOLT
0
V 0.1
0
–
–
06 LAI SPECIAL
MON
0
-
1
0
–
–
07 LAO MON
SELECT
0
-
1
0
–
–
08 LAO ACCEL
TIME
50 SEC 0.1
0
–
–
09 LAO DECEL
TIME
100 SEC 0.1
0
–
–
10
LDO
CMD
FWD.STOP
STOP
– 1 0 FWD
STOP
11
LDO
CMD
REV.STOP
STOP
– 1 0 REV
STOP
12 LAO FREQ
CMD
0
HZ 0.01
0
–
–
13 LAO MIN
FREQ
0
HZ 0.01
0
-
-
14
LAO
FREQ JUMP A
32767
HZ
0.01
0
-
-
15
LAO
FREQ JUMP B
32767
HZ
0.01
0
-
-
16 LDI ALARM
OUTPUT
0
–
1
0 ALARM -
17
LDI RUNNING STOP
– 1 0 RUN
STOP
18
LAO
PID SET PNT
0
PCT
0.01
0
-
-
19 LDO RESET
CMD
0
–
1
0 RESET -
20 LAO OVRD
TIME
1 HRS 1
0
–
–
21
LDI ASD
COMM NO - 1 0 YES
NO
22 LAO OPER
MODE
0
-
1
0
-
-
29 LDO DAY.NIGHT
DAY –
1
0 NIGHT DAY
99 LAO ERROR
STATUS
0
–
1
0
–
–
Notes:
•
•
Points not listed are not used in this application.
•
All points have the same value for English units and SI units.