2.4.2  Essential PID (PID3) 
 
FUN 156 
PID3 
Essential PID 
 
Expression 
 
Input  
─[ A  PID3  B  
  C ]
─  Output 
 
Function 
Performs PID (Proportional, Integral, Derivative) control which is a fundamental method of feed-back control. 
(Pre-derivative real PID algorithm) 
This PID3 instruction has the following features. 
• 
For derivative action, incomplete derivative is used to suppress interference of high-frequency noise and to 
expand the stable application range, 
• 
Controllability and stability are enhanced in case of limit operation for MV, by using digital PID algorithm 
succeeding to benefits of analog PID.  
• 
Auto, cascade and manual modes are supported in this instruction. 
• 
Digital filter is available for PV. 
• 
Direct / reverse operation is selectable. 
 
Execution condition 
Input Operation  Output 
OFF Initialization 
OFF 
ON 
Execute PID every setting interval 
ON when 
execution 
 
Operand 
 Name 
Device 
Register 
Con- 
Index 
  
X Y S L R Z T. C. I  O X 
W T  C D  F  I 
I J K 
stant
 
 
A  Top of input 
data 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
   
 
 
 
 
 
 
B Top of 
parameter 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
   
 
 
 
 
 
 
C Top of 
output data 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
   
 
 
 
 
 
 
 
 
 
Input data 
Control parameter 
Output data 
A  Process input value  
PVC 
B  Proportional gain  
K
P
 
C  Manipulation value  
MV 
A+1  A-mode set value   
ASV 
B+1  Integral time  
T
I
 
C+1  Last error 
e
n-1
 
A+2  C-mode set value  
CSV 
B+2  Derivative time  
T
D
 
C+2  Last derivative value  
D
n-1
 
A+3  M-mode MV input  
MMV 
B+3  Dead-band  
GP 
C+3  Last PV 
PV
n-1
 
A+4  MV tracking input  
TMV 
B+4  A-mode initial SV  
ISV 
C+4  Last SV 
SV
n-1
 
A+5  Mode setting  
MODE 
B+5  Input filter constant  
FT 
C+5  Integral remainder 
Ir 
   
B+6  ASV differential limit  
DSV 
C+6  Derivative remainder 
Dr 
   
B+7  MMV differential limit  DMMV 
C+7  Internal MV 
MV
n
 
  A-mode: Auto mode 
B+8  Initial status  
STS 
C+8  Internal counter 
C 
  C-mode: Cascade mode 
B+9  MV upper limit  
MH 
C+9  Control interval 
∆∆∆∆
t 
  M-mode: Manual mode 
B+10  MV lower limit  
ML 
   
   
B+11  MV differential limit  
DMV 
   
   
B+12  Control interval setting  
n