PROSEC T3H 
 
2. Expanded Functions 
 
 
2.4.5  Network data send (SEND) 
 
FUN 239 
SEND 
Network data send 
 
Expression 
 
Input  
─[ A  SEND  B ]─  Output 
 
 
Function 
This instruction sends the designated range of register data to another T3H through the network.  
(Network: TOSLINE-S20LP or Ethernet) 
The transfer source register (self-station) is designated by A+3 and A+4
The transfer destination register (target-station) is designated by A+5 and A+6
The transfer size (number of words) is designated by A+2. The maximum transfer size is 128 words (S20LP), 
or 485 words (Ethernet). 
The designation method of the target-station is different between S20LP and Ethernet. 
 
This instruction is also used for other functions of the Ethernet module. Refer to the Ethernet module (EN311) 
manual for detailed functions used for the EN311. 
 
Execution condition 
Input Operation Output 
ERF 
OFF No 
execution 
OFF 
 
ON During 
execution 
OFF 
 
 Normal 
complete 
ON 
 
 
When error is occurred (see Note) 
ON 
Set 
 
Operand 
 Name 
Device 
Register 
Con- 
Index 
  
X Y S L R Z T. C. I  O X 
W T  C D  F  I 
I J K 
stant
 
 
A Transfer 
parameter 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
   
 
 
 
 
 
 
B 
Status 
           
 
 
 
 
 
 
 
 
   
 
 
 
 
 
 
 
 
 
< In case of S20LP > 
< In case of Ethernet > 
 F C 
B  8 
 
C B 
8 7 
MID 
CH 
Target station No. 
MID CH 
(fixed) 
A+1 
0 (fixed) 
A+1 
Request command 
A+2 
Transfer size 
A+2 
Transfer size 
A+3 
Register type (self-station) 
A+3 
Register type (self-station) 
A+4 
Leading address (self-station) 
A+4 
Leading address (self-station) 
A+5 
Register type (target-station) 
A+5 
Register type (target-station) 
A+6 
Leading address (target-station) 
A+6 
Leading address (target-station) 
A+7 
Response time limit 
A+7 
Response time limit 
  
A+8 
Target-station IP address 
  
A+9 
 
  
A+10 
Target-station UDP port No. 
 
 
Note)  Parameters for the Ethernet varies depending on the request command. Above figure shows the 
 
 