Toshiba AS311 Manual De Usuario

Descargar
Página de 66
  
User’s 
Manual 
39
 
5. Operation Procedure 
 
 
 
5.2  Received message read sequence 
 
 
5.2.1 
Flag control timing 
 
 
 
 
In case of receiving a message, the following flags are used for handshaking between 
 
 
T3 and AS311. These flags are the bits of the I/O registers assigned to the AS311. 
 
 
Refer to section 4.1. 
 
 
 
Read ready 
Bit 7 of XW(n) for channel 1 or XW(n+1) for channel 2 
 
 
Receive complete 
Bit 6 of XW(n) for channel 1 or XW(n+1) for channel 2 
 
 
Receive error 
Bit 5 of XW(n) for channel 1 or XW(n+1) for channel 2 
 
 
 
Read start 
Bit 7 of YW(n+2) for channel 1 or YW(n+3) for channel 2 
 
 
 
The message receiving procedure is as follows. It is called “received message read 
  
sequence”. 
 
 
 
 
 
AS311 receives a message 
 
 
  
 
AS311 
sets 
Receive complete to ON 
 
 
  
 
T3 
sets 
Read start to ON 
 
 
 
 
   Normal receiving 
 
 
 
 
 
     Receiving error 
 
 
 
 
AS311 sets the message into buffer 
AS311 sets the error information into 
 
 
 
memory (receiving data area), and 
buffer memory (parameter area) 
 
 
 
sets the received message length into 
 
 
 
buffer memory (parameter area) 
 
 
 
 
 
 
 
 
 
 
  
 AS311 
sets 
Read ready to ON, and 
AS311 sets Receive error to ON, and 
  
  resets 
Receive complete to OFF 
resets Receive complete to OFF 
 
 
 
 
 
 
 
 
 
T3 reads the message form buffer 
T3 reads the error information from 
 
 
 
memory (receiving data area) 
buffer memory (parameter area) 
 
 
 
by READ instruction 
by READ instruction 
 
 
  
 
T3 
resets 
Read start to OFF 
T3 resets Read start to OFF 
 
 
  
  AS311 
resets 
Read ready to OFF 
AS311 resets Receive error to OFF