ASCII Interface Module (AS311) 
 
5. Operation Procedure 
 
 
 
5.7  Setting the time-out check time 
 
 
 
The default setting of the time-out check time is 1 second. The time-out check time 
 
 
can be changed by T3 program. The valid setting range is 0.1 to 60.0 seconds in 0.1 
 
 
second units. Refer to section 4.2.3. 
 
 
 
To change the time-out check time, write desired value into the AS311’s buffer memory 
 
 
address 25 (CH1 time-out check) and/or address 89 (CH2 time-out check), and  
 
 
execute the hot reset (refer to section 5.5).  
 
 
 
T3 program for this purpose is almost same as that for setting the trailing code (refer to 
 
 
section 5.6). Only the difference is writing the time-out check time instead of the trailing 
 
 
code. See Rung 2 of the following sample. In this sample, the channel 1 time-out check 
 
 
time is changed to 5 seconds. 
 
 
If the channel 2 time-out check time and/or the trailing code are also changed, write 
 
 
these data on the Main program Rung 2 before calling Subroutine No. 3 in the same 
  
manner. 
 
 
  
(Main 
program)