4. Connecting to the network 
 
4.1. Installation method 
(1) Attach DeviceNet cable to DeviceNet connector. (Refer to Section 2.1).   
(Be careful not to short-circuit adjacent terminals on DeviceNet connector). 
 
<Recommended cable> 
Thin branch cables: DeviceNet-specific thin cable. 
<Tightening torque> 
0.5 - 0.6 N·m 
Recommended screwdriver: Small flat-blade screwdriver (blade thickness: 0.6mm, 
blade length: 3.5mm or less)   
(2) Please set the terminating resistance if needed. 
<Terminating resistance specification> 
1/4 W - 121 ohm, 1% Metal Film 
(3) Using the DIP switch on the DeviceNet 
option
, set a MAC ID number and a baud rate. 
(Refer to Section 4.3).   
(4) Once all the parameters are set, the power must be cycled to the VF-AS1/PS1 for 
these changes to take effect. (Refer to Section 5.)