Toshiba CD332 Manual De Usuario

Descargar
Página de 32
10
 
Change Detect DC Input Module (CD332) 
2. Specifications 
 
 
 
2.1  General specifications 
 
Item Specifications 
Remarks
Power voltage 
5 Vdc (supplied from back plane bus) 
 
Current consumption 
0.3 A (5 Vdc) maximum 
Note (1) 
Environmental conditions 
Conforms to T3 specifications 
 
Withstand voltage 
1500 Vac - 1 minute 
Note (2) 
Size 
T3 I/O module size (1 slot) 
 
Weight 
Approx. 450 g 
 
 
 
Note (1)  The T3’s power supply module can supply maximum 7 A of internal 5 Vdc. 
 
 
Check that the internal 5 Vdc current consumption per one power supply  
 
 
module does not exceed the limit. 
 
Note (2)  Between external terminals and internal circuit. 
 
 
 
2.2  Functional specifications 
 
Item Specifications 
Remarks
Module type 
Change detect DC input  
 
I/O allocation type 
iX 1W 
 
Input type 
DC input, current source/sink  
 
Number of input points 
8 points (8 points/common) 
 
Rated input voltage 
12 - 24 Vdc 
 
Input voltage range 
10 - 30 Vdc 
 
Rated input current 
10 mA (at 24 Vdc) 
 
Minimum ON voltage 
9.6 Vdc 
 
Maximum OFF voltage 
3.5 Vdc 
 
ON delay time 
30 ms or less (normal mode) 
3.0 ms or less (high speed mode) 
Note (1) 
OFF delay time 
35 ms or less (normal mode) 
3.5 ms or less (high speed mode) 
Note (1) 
LED 
display 
DATA 0 - 7 
Input status display for all points,  
lit at ON, internal logic side 
 
 
STATUS 0 - 7 
Interrupt point display, returned to OFF 
by resetting the interrupt flag 
 
Interrupt function 
Generates interrupt signal for T3 when 
input status of each point is changed. 
Interrupt timing can be selected for each 
point either rising, falling or both edges. 
Note (2) 
Number of modules on T3 
Max. 8 modules 
 
 
 
Note (1)  The normal or high speed mode can be selected by internal jumper plug  
 
 
settings. Refer to section 3.1. 
 
 
The delay time includes the input filter and internal sampling. 
 
Note (2)  The interrupt timing is selected by DIP switches. Refer to section 3.2.