Examples of Instance 101/151
Access the inverter parameter is enabled using byte 4 to 6 of this Instance.
Set the communication number of the parameter to byte 4, 5 (Index), and the value to byte 6, 7 (Data).
In case of the monitor parameter “FE**”, 
the value becomes "communication number - 0x7000 (same as bit14, 15
set to 0)".
①  Read the parameter cmod (Command mode selection, communication number is 0003).
Instance
Byte
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
0
Hex.
5,  4
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
1
0x0003
Output Instance 101
7,  6
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Input Instance 151
5, 4
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
1
0x0003
(cmod is set 0.)
7, 6
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0x0000
②  Read the parameter f268 (Initial value of UP/DOWN frequency).
Instance
Byte
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
0
Hex.
5,  4
0
0
0
0
0
0
1
0
0
1
1
0
1
0
0
0
0x0268
Output Instance 101
7,  6
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Input Instance 151
5, 4
0
0
0
0
0
0
1
0
0
1
1
0
1
0
0
0
0x0268
(f268 is set 60.0Hz.)
7, 6
0
0
0
1
0
1
1
1
0
1
1
1
0
0
0
0
0x1770
③  Read the parameter fe04 (Voltage of DC bus).
Instance
Byte
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
0
Hex.
5, 4
0
0
1
1
1
1
1
0
0
0
0
0
0
1
0
0
0x3E04
Output Instance 101
7,  6
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Input Instance 151
5, 4
0
0
1
1
1
1
1
0
0
0
0
0
0
1
0
0
0x3E04
(fe04 is 94.49%.)
7, 6
0
0
1
0
0
1
0
0
1
1
1
0
1
0
0
1
0x24E9
④  Write “60 (Hz)” to the parameter sr1 (Preset speed 1, communication number is 0018).
Instance
Byte
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
0
Hex.
5, 4
1
0
0
0
0
0
0
0
0
0
0
1
1
0
0
0
0x8018
Output Instance 101
7,  6
0
0
0
1
0
1
1
1
0
1
1
1
0
0
0
0
0x1770
5, 4
1
0
0
0
0
0
0
0
0
0
0
1
1
0
0
0
0x8018
Input Instance 151 (OK)
7,  6
0
0
0
1
0
1
1
1
0
1
1
1
0
0
0
0
0x1770
Input Instance 151 (NG)
5, 4
1
1
0
0
0
0
0
0
0
0
0
1
1
0
0
0
0xC018
(Error code 
*
)
7,  6
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
0x0001
About byte 0 - 3, refer to section 3.4.5.2.
*
 Refer to following about the error code.
1
(= BN: 00000001):
: Data out of range
2
(= BN: 00000010):
: Bad address
3
(= BN: 00000011):
: Read only
4
(= BN: 00000100):
: Stop to modify or permission error
5
(= BN: 00000101):
: All other