3.4.6.8. FD01 (Inverter status (real time))
bit
Function
0
1
Note
0
FL
No output
Under output
-
1
EMG
No fault
Under fault
The  rtry status and the trip
retention status are also
regarded as tripped statuses.
2
ALARM
No alarm
Under alarm
-
3
(Reserved)
-
-
-
4
tHr2(VF2+tH2)
Motor 1
(THR1)
Motor 2
(THR2)
THR1: thr
THR2: f173
5
PI
PI enable
PI off
-
6
ACC1/ACC2
Acc./Dec. 1
(AD1)
Acc./Dec. 2
(AD2)
AD1: acc, dec
AD2: f500, f501
7
DC braking
OFF
DC braking
-
8
Jog
OFF
JOG RUN
-
9
Fw/Reverse
Fwd. RUN
Rev. RUN
-
10
Run/stop
STOP
RUN
-
11
Free run (ST)
ST=ON
ST=OFF
-
12
Emergency stop
No EMG. Stop Under EMG. Stop
-
13
READY with ST/RUN
ST = ON and RUN = ON in
addition to “ready for operation”
*
14
READY without ST/RUN
-
15
**
Local/Remote
Remote
Local
-
*
 Ready for operation: Initialization completed, not a stop due to a failure, no alarm issued, not moff,
not a forced stop due to ll, not a forced stop due to a momentary power failure.
**
 This function is reserved in VF-AS1.
3.4.6.9. FD00 (Output frequency (real time))
The current output frequency is read into 0.01Hz of units and by the hexadecimal number.
For example, when the output frequency is 80Hz, 0x1F40 (hexadecimal number) are read.
Since the minimum unit is 0.01%,
0x1F40 (Hex.)    = 8000(Dec.) * 0.01 = 80 (Hz)
Also about the following parameters, these are the same as this.
- FD22 (Feedback value of PID (real time)) ................................. Unit: 0.01Hz
- FD16 (PG feedback or Estimated speed (real time))................. Unit: 0.01Hz
- FD29 (Input power (real time))................................................... Unit: 0.01kW
- FD30 (Output power (real time)) ................................................ Unit: 0.01kW
3.4.6.10. FD03 (Output current (real time))
The output current is read into 0.01% of units and by the hexadecimal number.
For example, when the output current of the rated current 4.8A inverter is 50% (2.4A), 0x1388
(hexadecimal number) is read.
Since the minimum unit is 0.01%,
0x1388 (Hex.) = 5000 (Dec.) * 0.01 = 50 (%)
Also about the following parameters, these are the same as this.
- FD05 (Output voltage(real time) ................................................... Unit: 0.01% (V)
- FD04 (Voltage at DC bus (real time) ............................................ Unit: 0.01%(V)
- FD18 (Torque ............................................................................... Unit: 0.01% (Nm)
*
*
 When the motor information connected to the inverter set to the parameter (f405 - f415), torque
monitor value "100%" is same as the rated torque of a motor in general.