Toshiba G7 Manual De Usuario

Descargar
Página de 221
G7 ASD Operation Manual
181
Trip Monitor From ASD
The Trip Monitor From ASD function records the trip name of up to four trips and catalogs each trip as 
Most RecentSecond Most RecentThird Most Recent, and Fourth Most Recent. Once reset (Clear 
Trip
), the trip records are erased. If no trips have occurred since the last reset, No Fault is displayed for 
each trip record.
Note:
An improper ASD setup may cause some trips — reset the ASD to the Factory Default 
settings before pursuing a systemic malfunction (Program 
 Utility Parameters  
Type Reset 
 Restore Factory Defaults).
Trip Record at Monitor Screen
The at-trip condition of the last incurred trip may be viewed at the Monitor screen (see 
). The 
Monitor screen at-trip record is erased when the ASD is reset and may be viewed without the use of the 
RTC option.
Clearing a Trip
Once the cause of the trip has been corrected, performing a 
 re-enables the ASD for normal 
operation.
The record of a trip may also be cleared using either of the following methods:
• Cycling power (trip info may be saved via 
F602 
if desired),
• Pressing the Stop|Reset key twice,
• Remotely via the communications channel,
• Momentarily connecting terminal RES to CC of the Control Terminal Strip, or
• Via Program 
⇒ Utility Parameters ⇒ Type Reset ⇒ Clear Trip (clears Trip Monitor From ASD).