G7 ASD Operation Manual
The ASD input voltage should remain within 10% of the specified input voltage range. Input voltages 
approaching the upper or lower limit settings may require that the overvoltage and undervoltage stall 
protection level parameters, 
 an
, be adjusted. Voltages outside of the permissible tolerance 
should be avoided.
The frequency of the input power should be ±2 Hz of the specified input frequency.
Do not use an ASD with a motor that has a power rating that is higher than the rated output of the ASD.
The ASD is designed to operate NEMA B motors. Consult with your sales representative before using 
the ASD for special applications such as with an explosion-proof motor or applications with a piston 
load.
Do Not apply commercial power to the output terminals T1/UT2/V, or T3/W.
Disconnect the ASD from the motor before megging or applying a bypass voltage to the motor.
Interface problems may occur when an ASD is used in conjunction with some types of process 
controllers. Signal isolation may be required to prevent controller and/or ASD malfunction (contact 
your Toshiba sales representative or the process controller manufacturer for additional information 
about compatibility and signal isolation).
Use caution when setting the output frequency. Over speeding a motor decreases its ability to deliver 
torque and may result in damage to the motor and/or the driven equipment.
All G7 ASDs are equipped with internal DC bus fuses. However, not all G7 ASDs are equipped with 
internal primary power input fuses (HP dependent). When connecting two or more drives that have no 
internal fuse to the same power line as shown in 
, it will be necessary to select a circuit-
breaking configuration that will ensure that if a short circuit occurs in ASD 1, only MCCB2 trips, not 
MCCB1. If it is not feasible to use this configuration, insert a fuse between MCCB2 and ASD 1.
Mounting the ASD
Install the unit securely in a well ventilated area that is out of direct sunlight using the mounting holes 
on the rear of the ASD.
The ambient temperature rating for the G7 ASD is from 14 to 104° F (-10 to 40° C). The process of 
converting AC to DC, and then back to AC produces heat. During normal ASD operation, up to 5% of 
the input energy to the ASD may be dissipated as heat. If installing the ASD in a cabinet, ensure that 
there is adequate ventilation.
Do Not operate the ASD with the enclosure door open.
Figure 3. Circuit breaker configuration.
CAUTION