H9 ASD Installation and Operation Manual
Lead Length Specifications
Adhere to the NEC and any local codes during the installation of ASD/Motor systems. Excessive lead 
lengths may adversely effect the performance of the motor. Special cables are not required. Lead lengths 
from the ASD to the motor in excess of those listed in 
 may require filters to be added to the output 
of the ASD. 
 lists the suggested maximum lead lengths for the listed motor voltages.
Note:
Contact Toshiba for application assistance when using lead lengths in excess of those 
listed.
 
 
Exceeding the peak voltage rating or the allowable thermal rise time of the motor 
insulation will reduce the life expectancy of the motor.
 
 
When operating in the Vector Control mode the carrier frequency should be set to 
2.2 kHz or above.
Table 1.
Model
PWM Carrier 
Frequency
NEMA MG-1-1998 Section IV Part 31 
Compliant Motors
2
230 Volt
All
1000 feet
460 Volt
< 5 kHz
600 feet
≥ 5 kHz
300 feet