H9 ASD Installation and Operation Manual
39
Command Control Selections
The following is a listing with descriptions of the 
Command Mode (
) selections (Program 
⇒ 
Fundamental 
⇒ Standard Mode Selection ⇒ Command 
Mode Selection).
Settings:
0 — Terminal Block
Allows for Command control input via the 
Terminal Board.
2 — EOI Keypad
This setting is used for EOI command control.
3 — RS485 (4-wire)
Use this setting if using a remotely-mounted EOI for command control. Connect the EOI to the 
RJ45 connector of the Terminal Board.
4 — Communication Option Board
Use this setting if using the optional Communication Board for command control.
Frequency Control 
Selections
The following is a listing with descriptions of the 
Frequency Mode (
) selections (Program 
⇒ 
Fundamental 
⇒ Standard Mode Selection ⇒ 
Frequency Mode 1).
Settings:
1 — V/I 
This selection is used when a 0 to 10-volt DC 
analog input or a 0 – 20 mA DC current input 
is used as the speed control input. Only one input signal type may be used at a time. Set SW301 
to the desired signal type.
2 — RR
This selection is used for a 0 to 10-volt DC analog input signal.
3 — RX
This selection is used for a -10 to +10-volt DC analog input signal.
5 — EOI Keypad
This setting is used for EOI frequency control.
6 — RS485 (4-wire)
Use this setting if using a remotely-mounted EOI for frequency control. Connect the EOI to the 
RJ45 connector of the Terminal Board.
7 — Communication Option Board
Use this setting if using the optional Communication Board for frequency control.
8 — RX2 Option (AI1)
This selection is used for a -10 to +10-volt DC analog input signal.
(Default)