5.  Installing the Gateway 
The gateway’s installation procedure will vary slightly depending on the chosen 
mounting method and the networks that will be used. 
 
 
5.1  RS-485 Network in Use 
Note that in order to power the unit when not connecting to Toshiba ASDs via 
the common serial ports, the optional 120VAC/9VDC power supply (ICC part 
number 10456) or a user-supplied power source meeting the requirements 
outlined in section 12 must also be installed. 
 
1.  Mount the unit via the desired method (refer to page 12 for more 
information). 
2.  Connect the Modbus Plus network to the “NETWORK” DB9 connector.  Be 
sure to follow all published guidelines pertaining to Modbus Plus network 
connections, layout and routing. 
3.  Connect the RS485 network to the pluggable terminal block.  Refer to 
section 6 for detailed connection information.  Ensure that the terminal 
block is fully seated into the terminal block header, and route the network 
cable such that it is located well away from any electrical noise sources, 
such as ASD input power or motor wiring.  Also take care to route the 
cable away from any sharp edges or positions where it may be pinched. 
4.  Take a moment to verify that the gateway and all network cables have 
sufficient clearance from electrical noise sources such as drives, motors, or 
power-carrying electrical wiring. 
5.  Connect the power supply to the gateway’s “POWER” jack.