The default timeout time in all cases is 0, which disables network timeout 
handling.  When nonzero, timeout processing does not begin until after a valid 
network packet has been received by the unit on that port. 
 
When the timeout time is nonzero and a communication interruption is 
detected, the timeout enable selections for each point are inspected.  Those 
points that are found to have their timeout enable selections set to “enabled” 
will then have their configured timeout values automatically written to their 
assigned “source port” objects.  This mechanism provides for a flexible set of 
device failsafe conditions to be established on a point-by-point basis. 
 
 
13.3  Point Configuration 
As mentioned in section 1, the Network Gateway Series concept revolves 
around a central “point database”, containing the value and access 
characteristics for each network.  With respect to the Network Gateway Series, 
a “point” is simply an object that defines some sort of network access, mapping 
and configuration data, as well as a single “value” attribute that can be read 
from or written to by various communication ports or protocols. 
 
The only restriction placed on this “central clearinghouse” concept is that only 
one port can autonomously update the point’s value, “mirroring” its designated 
object for other protocols to access.  What this means is that although any 
protocol can read from or write to a point’s internal value, most of the time that 
point’s value will simply be mirroring a remote data object that resides on one of 
the gateway’s subnets.  The selection of what a specific point is to mirror is 
performed via its “source port” selection. 
 
For example, a point may be configured to contain Toshiba ASD parameter 
mapping and Modbus master ID and register mapping information.  However, 
because both of these protocols act as “master” protocols, only one of them 
can be allowed to continuously update the point’s value.  If both master 
protocols could simultaneously update the point’s internal value, it would 
erratically alternate back and forth between the values designated by the 
Toshiba parameter and Modbus register objects.  Any “slave” protocol (Modbus 
RTU slave, Modbus Plus MSTR reads & writes, etc.) can read from or write to a 
point at any time, but only the protocol designated by the point’s “source port” 
assignment will autonomously update the point’s value independent of any 
other protocol traffic. 
 
The “source port” designation also determines where a new point value will be 
written to when a “slave” protocol writes a new value to the point.  For example, 
if the Modbus Plus connection is used to write new data that changes the value 
of a point, how do we know where this new value will exit the gateway to arrive 
at its final destination?  The answer is that any new point values written by 
“slave” protocols will generate “write” transactions only on the “source port”.