Toshiba MBP-100 Manual De Usuario

Descargar
Página de 73
 
  
64
Address Description Register 
Value 
40050 
MSTR function (read) 
40051 
Error code 
Read Only 
40052 
Number of consecutive registers to read 
40053 Starting 
register 
40054 
Destination node address 
40055 
Master node address 
2.  Set the middle portion of the MSTR instruction to 40100.  This will be the 
starting address of the MSTR Data Area.  This is the location that will 
contain the read data returned from the MSTR transaction. 
Address Value 
40100 
Value of register 1 @ network address 2 
40101 
Value of register 2 @ network address 2 
3.  In this case, we are accessing two registers, so set the bottom portion of 
the MSTR instruction (“number of registers”) to 2.  In the case of MSTR 
reads, this number cannot be greater than 125 by definition. 
4.  Initiate the read command by closing internal relay 1.  The data response 
will be seen in the MSTR Data Area (register 40100). 
 
 
16.4  MSTR Write Example 
The following example demonstrates how to use the MSTR instruction to write 
4 registers starting at register 1 to an MBP-100 located at Modbus Plus network 
address 32. 
1.  Set up a ladder logic program as shown in Figure 37. 
2.  Set the top portion of the MSTR Instruction to 40060.  This will be the 
starting address of the MSTR Control Block. Set the Control Block 
registers to the following values: 
Address Description Register 
Value 
40060 
MSTR function (write) 
40061 
Error code 
Read Only 
40062 
Number of consecutive registers to write 
40063 Starting 
register 
40064 
Destination node address 
32 
40065 
Master node address 
3.  Set the middle portion of the MSTR instruction to 40200.  This will be the 
starting address of the MSTR Data Area.  This is the location that will 
contain the write data to be used in the MSTR write transaction.