Using the LED Indicators and Display for Troubleshooting
Section 14-2
---
---
E3
Server Con-
nection Error
An error 
occurred in 
transmission to 
the SNMP trap.
---
03C4
De-
tails: 
07xx
Perform one of the 
following:
• Correct  the 
SNMP trap set-
tings.
• Check the com-
munications path 
(EtherNet/IP Unit 
or built-in Ether-
Net/IP port, cable 
connections, 
hubs, routers, and 
servers) and cor-
rect any prob-
lems.
---
Lit red
F0
IP Address 
Duplication
The IP address 
of the EtherNet/
IP Unit or built-in 
EtherNet/IP port 
is the same as 
the IP address 
set for another 
node.
• The Unit will be 
offline and unable to 
communicate. Errors 
will be returned to all 
communications 
requests.
• Data exchanges 
(refreshing) will con-
tinue with the CPU 
Unit.
The Unit Error 
Occurred Flag (n+10, 
bit 00), Network Error 
Occurred Flag (n+10, 
bit 01), and IP 
Address Duplication 
Error Flag (n+10, bit 
06) will go ON.
0211
Check the IP 
addresses set on 
other nodes. 
Restart the Ether-
Net/IP Unit or built-
in EtherNet/IP port 
after correcting the 
IP address settings 
to eliminate dupli-
cations.
Flashing 
red
---
F3
Address mis-
match
The target IP 
address conver-
sion method is 
set to Automatic 
generation
, but 
the last byte of 
the local IP 
address does 
not match the 
value set on the 
Node Address 
Setting Switch.
• Operation will con-
tinue with the set IP 
address as the local 
IP address.
The Address Mis-
match Flag (n+14, 
bit 14) will turn ON.
---
Check the IP 
address and the 
Node Address Set-
ting Switch setting.
Indicator
Error
Cause
Unit operation (Flag 
status)
Error 
log
(hex)
Countermeasure
MS
NS
7-segment