GE 1019071 Manual De Usuario
2.2.10 UPS command group
The UPS command group allows monitoring and configuration of the managed UPS system.
Command Parameters
Description
upsinfo
(*)
Show detailed UPS information
upstest
(*)
Start/Stop UPS tests
upscontrol
(*)
Control the UPS (1-ph/SP versions ONLY)
upsconfig
(*)
Configure UPS parameters
attacheddevice [device]
Set UPS attached device
[device]
[device]
Device which is powered/protected by the UPS
NOTE: Maximum length 63 chars. If this parameter contain
blanks or special characters it shall be specified in between
double quotation marks (“...”)
blanks or special characters it shall be specified in between
double quotation marks (“...”)
alarmdelay
[time]
Set alarm delay time (1-ph/SP version ONLY)
[time] Time in seconds before alarm notification
NOTE: This parameters is factory set to its ideal value and
shall not be changed unless instructed to do so
[time] Time in seconds before alarm notification
NOTE: This parameters is factory set to its ideal value and
shall not be changed unless instructed to do so
retrydelay
[time]
Set retry delay time (1-ph/SP version ONLY)
[time] Time in seconds between re-connection attempts
NOTE: This parameters is factory set to its ideal value and
shall not be changed unless instructed to do so
[time] Time in seconds between re-connection attempts
NOTE: This parameters is factory set to its ideal value and
shall not be changed unless instructed to do so
retrycount
[count]
Set retry count (1-ph/SP version ONLY)
[count] Number of re-connection attempts
NOTE: This parameters is factory set to its ideal value and
shall not be changed unless instructed to do so
[count] Number of re-connection attempts
NOTE: This parameters is factory set to its ideal value and
shall not be changed unless instructed to do so
serialbypass
on | off
Enable/disable the serialbypass functionality
NOTE: This command is offered for UPS service access ONLY.
It use outside of this scope is not recommended (enabling
this functionality stops the UPS monitoring
NOTE: This command is offered for UPS service access ONLY.
It use outside of this scope is not recommended (enabling
this functionality stops the UPS monitoring
Show/Set card address on the IMV bus
[address]
[address]
Card address in the range 0, 54-57
NOTE: This setting may overrides the HW setting through the
dip-switches on the card. Setting this parameter to 0 reverts
to the HW settings.
This setting becomes active only after reboot (save the
settings!)
dip-switches on the card. Setting this parameter to 0 reverts
to the HW settings.
This setting becomes active only after reboot (save the
settings!)
[address]
cardaddress
Enable/disable write commands to the UPS
Setting readonlymode to on will stop any write operation
towards the UPS (the SNMP/Web adapter will effectively
switch to read-only mode). The UPS Test, Control and Config
web pages will not be shown in the navigator bar.
Setting readonlymode to on will stop any write operation
towards the UPS (the SNMP/Web adapter will effectively
switch to read-only mode). The UPS Test, Control and Config
web pages will not be shown in the navigator bar.
[on | off]
readonlymode
Caution! Once enabled, this setting may not be reverted.
NOTE: 1-ph/SP versions ONLY
NOTE: 1-ph/SP versions ONLY
Modifications reserved
Page 23/58
OPM_CNT_SNM_BAS_CRD_1GB_V012.doc
Operating Manual SNMP/Web Adapter