Delta Electronics DVPEN01-SL Manual De Usuario

Descargar
Página de 54
Ethernet Communication Module DVPEN01-SL
 
DVP-PLC Application Manual 
45
5.  After all the settings in DVPEN01-SL are completed, compile the ladder diagram in the MPU and 
download it to the MPU. See below for the program design: 
END
X0
T0
K100
K3
K1
K4
K5
K6
K1
X0
T0
K100
K1
K1
T0
K100
K1
K1
T0
K100
K1
K1
Y0
Y0
 
Explanations: 
• 
If the rising-edge of X0 is triggered, X0 will go from Off to On. Write “1” into CR#3 of 
DVPEN01-SL, and the first E-Mail will be sent out. 
• 
If the falling-edge of X0 is triggered, X0 will go from On to Off. Write “1” into CR#4 of 
DVPEN01-SL, and the second E-Mail will be sent out. 
• 
If the rising-edge of Y0 is triggered, Y0 will go from Off to On. Write “1” into CR#5 of 
DVPEN01-SL, and the third E-Mail will be sent out. 
• 
If the falling-edge of Y0 is triggered, Y0 will go from On to Off. Write “1” into CR#6 of 
DVPEN01-SL, and the fourth E-Mail will be sent out. 
6.9  Application of Data Exchange (1) 
Application 
Writing the time in RTC in PLC_B into D0 ~ D6 of PLC_A 
Network 
requirement 
(1)  Adopting static IP. 
(2)  IP of PLC_A: 192.168.0.4 
(3)  IP of PLC_B: 192.168.0.5” 
(4)  Update from PLC_B to PLC_A 
 
1.  See 6.1 for how to set up the communication. 
2.  Open the setup page of PLC_B and switch to “Data Exchange” page.