CANopen Communication Module DVPCOPM-SL 
DVP-PLC Application Manual 
22 
Request Message 
PLC device 
 
15 14 13 12 11 10
9
8
7
2
1
0
D6250 ReqID 
Command 
D6251 
Reserved 
Size (fixed to 04Hex) 
D6252 
Message Header 
Type (fixed to 03Hex) 
MAC ID 
D6253 Reserved 
NMT 
service 
code 
D6254 
Message Data 
Reserved MAC 
ID 
z  Command: Fixed to “01Hex”. 
z  ReqID: The request ID. Whenever an NMT request message is sent out, the message will be given a ReqID 
for the CANopen master to identify. For the next NMT request message to be sent out, you have to change 
the ID number. Range of ReqID: 00Hex ~ FFHex. 
z  MAC ID: The node address of the target equipment on CANopen network. 
z NMT 
service 
code 
z  01Hex: Enable remote node; 02Hex: Disable remote node; 80Hex: Enter pre-operational status; 81Hex: 
Reset application; 82Hex: Reset communication 
Example: If you would like to stop node 03 equipment on CANopen network, you have to set NMT service 
code to “02Hex” and MAC ID to “03". 
5.4 
Structure of Emergency Request Message 
See the table below for the format of Emergency request message: 
Request Message 
PLC device 
 
15 14 13 12 11 10
9
8
7
2
1
0
D6250 ReqID 
Command 
D6251 
Reserved 
Size (fixed to 0) 
D6252 
Message Header 
Type (fixed to 04Hex) 
MAC ID 
D6253 ~ D6281 
Message Data 
Reserved 
See the table below for the format of Emergency response message: 
Response Message 
PLC device 
 
15 14 13 12 11 10
9
8
7
2
1
0
D6000 ReqID 
Status 
D6001 Reserved 
Size 
(2A 
Hex) 
D6002 
Message Header 
Type (04Hex) 
MAC ID 
D6003 
Total number of data 
Number of data stored 
D6004 
Datum 1 
Datum 0 
D6005 
Datum 3 
Datum 2 
D6006 
Datum 5 
Datum 4 
D6007 
Datum 7 
Datum 6 
D6008 ~ D6011 
Emergency2 
D6012 ~ D6015 
Emergency3 
D6016 ~ D6019 
Message Data 
Emergency4