PG-02 Terminal Descriptions 
Terminals 
 
Terminal Symbols 
Descriptions 
VP 
Power source of PG-02 (FSW1 can be switched to 12V or 5V)   
Output Voltage: (+12VDC 
±5% 200mA) or (+5VDC ±2% 400mA) 
DCM 
Power source (VP) and input signal (A, B) common 
 
Input signal from Pulse Generator. Input type is selected by FSW2. 
Maximum 500KP/Sec   
A/O, B/O 
PG-02 output signal for use with RPM Meter. 
Maximum DC24V 300mA 
COM 
PG-02 output signal (A/O, B/O) common. 
 
Wiring Notes 
 
The control, power supply and motor leads must be laid separately. They 
must not be fed through the same cable conduit / trunking. 
 
1.  Please use a shield cable to prevent interference. Do not run control wire parallel to any 
high voltage AC power line (220 V and up). 
2.  Connect shielded wire to 
 E only.  
3.  Recommended wire size 0.21 to 0.81mm
(AWG24 to AWG18). 
4. Wire 
length: 
Types of Pulse 
Generators 
Maximum Wire Length
Wire Gauge 
Output Voltage 
50m 
Open Collector 
50m 
Line Driver 
300m 
Complementary 70m 
1.25mm