Group 2 Digital Output/Input Parameter 
 
Parameters Functions 
Settings 
Factory 
Setting
Customer
a 02-00  Source of Frequency 
Command 
00: via keypad   
01: via analog input AVI 
02: via analog input ACI1 
03: via analog input ACI2 
04: via RS485 serial 
communication 
05: via External Reference 
00  
a 02-01  Source of Operation 
Command 
00: Controlled by the digital 
keypad  
01: Controlled by the external 
terminals, keypad STOP 
enabled.  
02: Controlled by external 
terminals, keypad STOP 
disabled.  
03: Controlled by the RS-485 
communication interface, 
keypad STOP enabled.   
04: Controlled by the RS-485 
communication interface, 
keypad STOP disabled. 
00  
 
02-02  Stop Method 
00:Stop = ramp to stop, E.F. 
(External Fault) = coast to 
stop 
01:Stop = coast to stop, E.F. = 
coast to stop 
02:Stop = ramp to stop, E.F. = 
ramp to stop 
03:Stop = coast to stop, E.F. = 
ramp to stop   
00  
a
02-03 PWM 
Carrier 
Frequency 
Selections 
1~10HP: 4000~10000Hz 
15~30HP: 3000~9000Hz 
40HP: 2000~6000Hz 
9000Hz
6000Hz
4000Hz
 
 02-04 Forward/Reverse 
Enable  00: 
Forward 
enabled 
01: Reverse disabled 
02: Forward disabled 
00  
 02-05 2-wire/3-wire 
Operation 
Control Modes 
00: 2-wire (#1), FWD/STOP, 
REV/STOP 
01: 2-wire (#2), RUN/STOP, 
REV/FWD 
02: 3-wire 
00  
 
02-06  Line Start Lockout 
00: Disabled   
01: Enabled 
01