Group 6 Protection Function Parameters (Twice the value for 460V class)
 
 
Parameters Functions 
Settings 
Factory 
Setting
Customer
 06-00 Over-voltage 
Stall 
Prevention 230V: 
330.0~410.0VDC 
460V: 660.0~820.0VDC 
00: Disable 
390.0
780.0
 
 06-01 Over-current 
Stall 
Prevention 
during Acceleration 
20~150% 
00: Disable 
120
 
 06-02 Over-current 
Stall 
Prevention 
during operation 
20~150% 
00: Disable 
120
 
 06-03 Over-torque 
Detection 
Selection 
00: Over-torque detection 
disabled.  
01: Over-torque detection enabled 
during constant speed 
operation (OL2), and operation 
continues.  
02: Over-torque detection enabled 
during constant speed 
operation (OL2), and operation 
halted. 
03: Over-torque detection enabled 
during operation (OL2), and 
operation continues.   
04: Over-torque detection enabled 
during operation (OL2), and 
operation halted. 
00  
 06-04 Over-torque 
Detection 
Level 30~150% 
110
 
 06-05 Over-torque 
Detection 
Time 0.1~60.0 
Sec 
0.1 
 
 06-06 Electronic 
Thermal 
Relay 
Selection 
00: Operate disabled. 
01: Operate with a standard motor.
02: Operate with a special motor. 
02  
 06-07 Electronic 
Thermal 
Characteristic 
30~600 Sec 
60 
 
 
06-08  Low Current Detection Level 00~100% (00 disabled) 
00 
 
 
06-09  Low Current Detection Time 0.1~ 3600.0 Sec 
10.0
 
 
06-10  Low Current Detection 
Treatment 
00: Warn and ramp to stop   
01: Warn and coast to stop 
02: Warn and keep operating 
01  
 06-11 Present 
Fault 
Record 
00 
 
 
06-12  Second Most Recent Fault 
Record 
00  
 
06-13    Third Most Recent Fault 
Record 
00: No fault   
01: Oc (over-current) 
02: Ov (over-voltage) 
03: OH (over temperature) 
04: OL (over load) 
00