Delta Electronics VFD-F Series Manual De Usuario
B
VFD-F Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
B-5
B.1.2 Specifications for Brake Unit
Voltage Class
230V Series
460V Series
Model Number VFDB-
□□□□
2015 2022 4030 4045 4132
Max. Motor Power (kW)
15
22
30
45
132
Max. Peak Discharge
Current (A) 10%ED
Current (A) 10%ED
40 60 40 60 240
Continuous Discharge
Current (A)
Current (A)
15 20 15 18 75
Ou
tp
ut
Ra
ting
Brake Start-up Voltage
(DC)
(DC)
330/345/360/380/400/415
±3V
660/690/720/760/800/830
±6V
618/642/667/
690/725/750±6V
In
put
Rati
n
g
DC Voltage
200~400VDC
400~800VDC
480~750VDC
Heat Sink Overheat
Temperature over +95
°C (203
o
F)
Alarm Output
RELAY contact 5A120Vac/28Vdc(RA, RB, RC)
Pr
ot
ec
tion
Power Charge Display
Blackout until bus (+~-) voltage is below 50VDC
Installation Location
Indoor (no corrosive gases, metallic dust)
Operating Temperature -10℃~+50℃
Storage Temperature
-20℃~+60℃
Humidity 90%
Non-condensing
E
nvir
onm
en
t
Vibration
9.8m/S
2
(1G) under 20Hz
2m/S
2
(0.2G) at 20~50Hz
Wall-mounted Enclosed Type
IP50
IP10