5.10 Group 9: Communication Parameters 
09 - 00 
Communication Address 
a
 
Factory Setting:  01
      
Settings 
01-254 
00: Disable 
  If the AC drive is controlled by RS-485 serial communication, the communication address 
for this drive must be set via this parameter. 
09 - 01 
Transmission Speed (Baud Rate) 
a
 
Factory Setting:  01
      
Settings 
00: Baud rate 4800 
01: Baud rate 9600 
02: Baud rate 19200 
03: Baud rate 38400 
  This parameter determines transmission speed of AC drive communication.  
09 - 02 
Transmission Fault Treatment 
a
 
Factory Setting:  03
      
Settings 
00: Warn and keep operating  
01: Warn and RAMP to stop  
02: Warn and COAST to stop  
03: No warning and no display 
  This parameter is set to detect if an error occurs and take actions. 
09 - 03 
 Time-out Detection during Transmission 
Factory Setting: 00
 Settings 
00: Disable  
01: Enable 
  This parameter is used for ASCII mode. When this parameter is set to 01, indicates that the 
over time detection is enable, the time slot between each character can’t exceed 500 ms.  
09 - 04 
Communication Format 
Factory Setting: 00
 Settings 
00: 7-bit for ASCII 
01: 8-bit for ASCII  
02: 8-bit for RTU 
 
09 - 05 
Even/Odd Parity and Stopping Parity Setting  
Factory Setting: 00
 Settings 
00: None parity + 2 stop bit 
01: Even parity + 2 stop bit 
02: Odd parity + 2 stop bit 
03: None parity + 1 stop bit 
04: Even parity + 1 stop bit 
05: Odd parity + 1 stop bit 
  This parameter determines the communication format of serial communication.