Chapter 6  Control Modes of Operation|ASDA-AB Series
 
6-4  
 
Revision March 2008, Doc. Name: 2007PDD23000011
 
Position 
Command 
POS2
POS1 
POS0
CTRG  Parameters
Description 
P1-23 
Rotation number (+/- 30000) 
P5  1 0 0 
 
P1-24 
Pulses (+/- max cnt) 
P1-25 
Rotation number (+/- 30000) 
P6  1 0 1 
 
P1-26 
Pulses (+/- max cnt) 
P1-27 
Rotation number (+/- 30000) 
P7  1 1 0 
 
P1-28 
Pulses (+/- max cnt) 
P1-29 
Rotation number (+/- 30000) 
P8  1 1 1 
 
P1-30 
Pulses (+/- max cnt) 
State of POS0~2: 0 indicates the contact is OFF (Normally Open) 
 
1 indicates the contact is ON (Normally Closed) 
CTRG : the instant time when the contact changes from 0 (open) to 1 (closed). 
The application of absolute and incremental position control is various and multiple. This kind of position 
control is equal to a simple sequence control. User can easily complete the cycle running by using the 
above table. For example, the position command, P1 is 10 running and P2 is 20 running. Give the 
position command P1 first and then give the position command P2. The difference between absolute 
and incremental position control is shown as the figure below: 
20 turns
10 turns
20 turns
10 turns
Absolute Type
Incremental Type
 
 
6.2.3  Structure of Position Control Mode 
Basic Structure: