Delta Electronics RTU-DNET Manual De Usuario

Descargar
Página de 41
DeviceNet Remote I/O Communication Module RTU-DNET
 
DVP-PLC Application Manual 
Baud rates 
125 kbps; 250 kbps; 500 kbps 
„ Electrical specification 
Voltage 
11 ~ 25 VDC, supplied by internal bus from PLC MPU 
Current 
28mA (typical), 125mA impulse current (24 VDC) 
„ Environment 
Noise immunity 
ESD (IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge 
EFT (IEC 61131-2, IEC 61000-4-4): Power Line: 2KV, Digital I/O: 1KV 
Analog & Communication I/O: 1KV 
Damped-Oscillatory Wave: Power Line: 1KV, Digital I/O: 1KV 
RS (IEC 61131-2, IEC 61000-4-3): 26MHz ~ 1GHz, 10V/m 
Operation 
0ºC ~ 55ºC (temperature); 50 ~ 95% (humidity); pollution degree 2 
Storage 
-25ºC ~ 70ºC (temperature); 5 ~ 95% (humidity) 
Vibration/shock 
resistance 
Standard: IEC 61131-2, IEC 68-2-6 (TEST Fc)/IEC 61131-2 & IEC 68-2-27 (TEST 
Ea) 
Certificates 
IEC 61131-2, UL508 
1.4  Extension Modules Connectable to RTU-DNET 
R
T
U
-D
N
E
T
D
V
P
-0
2
D
A
D
V
P
-0
8
S
T
D
V
P
-1
6
S
P
D
V
P
-0
4
A
D
D
V
P
-0
4
T
C
D
V
P
-0
4
P
T
 
„  DVP Slim DI/DO extension units connectable to RTU-DNET 
Slim DI/DO 
(model name) 
I/O mapping data 
(DeviceNet  → RTU-DNET) 
I/O mapping data 
(RTU-DNET  → DeviceNet) 
DVP-08SM11N N/A 
bits 
DVP-08SN11R/T 8 
bits 
N/A 
DVP-08SP11R/T 
8 bits 
8 bits 
DVP-16SP11R/T 
8 bits 
8 bits 
DVP-08ST N/A 
bits 
„  Special modules connectable to RTU-DNET 
Default I/O mapping data 
(DeviceNet  → RTU-DNET) 
I/O mapping data 
(RTU-DNET  → DeviceNet) 
Special module 
(model name) 
Start CR 
Length (words) 
Start CR 
Length (words) 
DVP-02DA CR#10  2 
N/A  N/A 
DVP-04DA CR#6  4  N/A N/A 
DVP-04AD N/A N/A 
CR#12 
DVP-06AD N/A N/A 
CR#12