Chapter 5 Parameters|VFD-S Series 
Revision August 2006, SE08, SW V2.61 
5-13
 
  Two-wire/three-wire 
Applications Purpose 
Functions 
Related 
Parameters 
General application 
To run, stop, 
forward and 
reverse by external 
terminals 
FWD/STOP
REV/STOP
M0 "Open": Stop, "Close": FWD Run
M1 "Open": Stop, "Close":REV Run
GND
 
 
RUN/STOP
REV/FWD
M0 "Open": Stop, "Close": Run
M1 "Open": FWD, "Close":REV
GND
 
 
3-wire 
STOP
RUN
RUN/FWD
M0 Run command, Runs when "close" 
M2 Stop command, stops when "Open"
M1 REV/FWD Run selection
"Open": FWD Run
"Close": REV Run
GND
 
4-04~4-08 
 
  Frequency Hold 
Applications Purpose 
Functions 
Related 
Parameters 
General application 
Acceleration/ 
deceleration pause
Hold output frequency during 
Acceleration/deceleration 
4-04~4-08 
 
  Auto Restart after Fault 
Applications Purpose 
Functions 
Related 
Parameters 
Air conditioners, 
remote pumps 
For continuous and 
reliable operation 
without operator 
intervention 
The AC motor drive can be 
restarted/reset automatically up to 10 
times after a fault occurs. 
8-14 
 
  Emergency Stop by DC Braking 
Applications Purpose 
Functions 
Related 
Parameters 
High-speed rotors 
Emergency stop 
without brake 
resistor 
AC motor drive can use DC braking 
for emergency stop when quick stop is 
needed without brake resistor. When 
used often, take motor cooling into 
consideration. 
8-00 
8-02 
8-03