Delta Electronics VFD-S Manual De Usuario

Descargar
Página de 185
Appendix B  Accessories|VFD-S Series 
Revision August 2008, SE09, SW V2.61 
B-13
 
 
Application 3 
Question 
Used to improve the input power factor, to 
reduce harmonics and provide protection 
from AC line disturbances (surges, switching 
spikes, short interruptions, etc.). The AC line 
reactor should be installed when the power 
supply capacity is 500kVA or more and 
exceeds 6 times the inverter capacity, or the 
mains wiring distance 
10m. 
When the mains power capacity is too large, 
line impedance will be small and the charge 
current will be too high. This may damage AC 
motor drive due to higher rectifier 
temperature. 
 
Correct wiring 
large-capacity
     power
reactor
small-capacity
AC motor drive
motor