Delta Electronics VFD-S Manual De Usuario

Descargar
Página de 185
 
Revision August 2008, SE09, SW V2.61
 
3-1
 
Chapter 3 Start Up 
3.1 Preparations before Start-up 
Carefully check the following items before proceeding. 
„ 
Make sure that the wiring is correct. In particular, check that the output terminals U/T1, 
V/T2, W/T3 are NOT connected to power and that the drive is well grounded. 
„ 
Verify that there are no short-circuits between terminals and from terminals to ground or 
mains power. 
„ 
Check for loose terminals, connectors or screws. 
„ 
Verify that no other equipment is connected to the AC motor.  
„ 
Make sure that all switches are OFF before applying power to ensure that the AC motor 
drive doesn’t start running and there is no abnormal operation after applying power. 
„ 
Make sure that the front cover is correctly installed before applying power. 
„ 
Do NOT operate the AC motor drive with humid hands. 
„ 
Check the following items after applying power: The display without digital keypad should 
be as following. 
-The keypad should light up as follows (normal status with no error) 
RUN
FWD
REV
STOP
MIN. MAX.
RUN
STOP/RESET
MODE
PROG
DATA
 
- If the drive has built-in fan, it should run. 
When power is ON,  
LEDs “STOP” and “FWD” 
should light up. The 
display will show “F60.0”.