Chapter 5
 
Troubleshooting| 
5-2
 
Revision August 2008, 03VE, SW V2.04
 
5.2 Ground Fault 
 
 
GFF
Ground fault
No
Yes
If output circuit(cable or 
motor) of AC motor drive 
is grounded?
Remove grounding
Maybe AC motor drive  has 
malfunction or misoperation
due to noise. Please 
contact DELTA.
 
5.3 Over Voltage (OV) 
 
 
 
Over voltage
Yes
No
Yes
No
No
No
If voltage is within 
specification
Reduce voltage to
be within spec.
If over-voltage is occurred without load
Maybe AC motor drive
has malfunction or  
misoperation due to
noise. Please contact
DELTA.
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
No
No
When OV occurs, check if the 
voltage of DC BUS is greater
than protection value
If OV occurs when 
sudden acceleration
stops
Increase
deceleration
time
Increase setting time
Increase
acceleration
time
Reduce moment 
of inertia
Reduce moment of load  inertia
Use brake unit or DC brake
Need to check control method. Please contact DELTA.
Need to considerate to
use brake unit  and 
DC brake