Delta Electronics VFD-VE Series Manual De Usuario

Descargar
Página de 291
 
Revision August 2008, 03VE, SW V2.04
 
6-1
 
Chapter 6 Fault Code Information and Maintenance
 
6.1 Fault Code Information 
The AC motor drive has a comprehensive fault diagnostic system that includes several different 
alarms and fault messages. Once a fault is detected, the corresponding protective functions will be 
activated. The following faults are displayed as shown on the AC motor drive digital keypad display. 
The six most recent faults can be read from the digital keypad or communication. 
NOTE
 
Wait 5 seconds after a fault has been cleared before performing reset via keypad of input terminal. 
6.1.1 Common Problems and Solutions 
Fault Name 
Fault Descriptions 
Corrective Actions 
 
Over-current during 
acceleration 
(Output current 
exceeds triple rated 
current during 
acceleration.) 
1. 
Short-circuit at motor output: Check for 
possible poor insulation at the output 
lines. 
2. 
Acceleration Time too short: Increase the 
Acceleration Time. 
3. 
AC motor drive output power is too small: 
Replace the AC motor drive with the next 
higher power model. 
 
Over-current during 
deceleration 
(Output current 
exceeds triple rated 
current during 
deceleration.) 
1. 
Short-circuit at motor output: Check for 
possible poor insulation at the output line.
2. 
Deceleration Time too short: Increase the 
Deceleration Time. 
3. 
AC motor drive output power is too small: 
Replace the AC motor drive with the next 
higher power model. 
 
Over-current during 
steady state 
operation 
(Output current 
exceeds triple rated 
current during 
constant speed.) 
1. 
Short-circuit at motor output: Check for 
possible poor insulation at the output line.
2. 
Sudden increase in motor loading: Check 
for possible motor stall. 
3. 
AC motor drive output power is too small: 
Replace the AC motor drive with the next 
higher power model. 
 
Hardware failure in 
current detection 
Return to the factory