Chapter 6 Fault Code Information and Maintenance| 
6-6
 
Revision August 2008, 03VE, SW V2.04
 
Fault Name 
Fault Descriptions 
Corrective Actions 
 
It will be displayed 
when slip exceeds 
Pr.05-26 setting and 
time exceeds Pr.05-
27 setting. 
1. 
Check if motor parameter is correct (please 
decrease the load if overload 
2. 
Check the settings of Pr.05-26 and Pr.05-
27 
 
It will be displayed 
when broken belt 
detection function is 
enabled(Pr.08-59), 
allowance error is 
higher than Pr.08-61 
and detection time 
exceeds Pr.08-62.  
1. 
Check if the belt is broken 
2. 
Check the settings of Pr.08-60, Pr.08-62 
and Pr.08-63 
 
It will be displayed 
when the allowance 
error of tension PID 
feedback exceeds 
Pr.08-63 setting and 
allowance error 
detection time 
exceeds Pr.08-64 
setting. 
1. 
Check if the PID feedback is correct 
2. 
Check if the material is broken 
3. 
Check the settings of Pr.08-63 and Pr.08-
64 
 
6.1.2 Reset 
There are three methods to reset the AC motor drive after solving the fault: 
1. Press 
RESET
STOP
 key on KPV-CE01. 
2. 
Set external terminal to “RESET” (set one of Pr.02-01~Pr.02-06/ Pr.02-23~Pr.02-30 to 5) 
and then set to be ON. 
3. Send 
“RESET” 
command by communication. 
 
NOTE
  
Make sure that RUN command or signal is OFF before executing RESET to prevent damage or 
personal injury due to immediate operation.