Chapter 2 Installation and Wiring 
After removing the front cover (see chapter 1.2.3 for details), check if the power and control terminals 
are clear. Be sure to observe the following precautions when wiring. 
 
„ General 
Wiring 
Information 
Applicable Codes 
All VFD-VE series are Underwriters Laboratories, Inc. (UL) and Canadian Underwriters 
Laboratories (cUL) listed, and therefore comply with the requirements of the National 
Electrical Code (NEC) and the Canadian Electrical Code (CEC). 
 
Installation intended to meet the UL and cUL requirements must follow the instructions 
provided in “Wiring Notes” as a minimum standard. Follow all local codes that exceed UL 
and cUL requirements. Refer to the technical data label affixed to the AC motor drive and 
the motor nameplate for electrical data. 
 
The "Line Fuse Specification" in Appendix B, lists the recommended fuse part number for 
each VFD-VE Series part number.  These fuses (or equivalent) must be used on all 
installations where compliance with U.L. standards is a required. 
CAUTION!
 
1. 
Make sure that power is only applied to the R/L1, S/L2, T/L3 terminals. Failure to comply may 
result in damage to the equipment. The voltage and current should lie within the range as 
indicated on the nameplate. 
2. 
Check following items after finishing the wiring: 
A.  Are all connections correct? 
B.  No loose wires?
 
C.  No short-circuits between terminals or to ground?
 
DANGER!
 
1. 
A charge may still remain in the DC bus capacitors with hazardous voltages even if the power 
has been turned off. To prevent personal injury, please ensure that the power is turned off and 
wait ten minutes for the capacitors to discharge to safe voltage levels before opening the AC 
motor drive. 
2. 
All the units must be grounded directly to a common ground terminal to prevent lightning strike 
or electric shock. 
3. 
Only qualified personnel familiar with AC motor drives is allowed to perform installation, wiring 
and commissioning. 
4. 
Make sure that the power is off before doing any wiring to prevent electric shock.