Chapter 4 Parameters| 
4-38
 
Revision August 2008, 03VE, SW V2.04
 
4.3 Description of Parameter Settings 
Group 0 User Parameters 
: This parameter can be set during operation. 
00-00 
Identity Code of the AC Motor Drive  
Control 
mode
 
VF VFPG SVC 
FOCPG TQRPG
 
Factory setting:  ##
 Settings 
Read 
Only 
00-01 
Rated Current Display of the AC Motor Drive 
Control 
mode
 
VF VFPG SVC 
FOCPG TQRPG
 
Factory setting:  ##
 Settings 
Read 
Only 
 
Pr. 00-00 displays the identity code of the AC motor drive. The capacity, rated current, rated 
voltage and the max. carrier frequency relate to the identity code. Users can use the following 
table to check how the rated current, rated voltage and max. carrier frequency of the AC motor 
drive correspond to the identity code. 
 
Pr.00-01 displays the rated current of the AC motor drive. By reading this parameter the user 
can check if the AC motor drive is correct. 
 
The factory setting is rated current for the constant torque and can be set in Pr.00-12. 
 
230V Series 
kW 
0.75 1.5 2.2 3.7 5.5 7.5  11  15 18.5
22  30  37 
HP 
1.0 2.0 3.0 5.0 7.5 10 15 20 25 30 40 50 
Pr.00-00  4  6  8  10 12 14 16 18 20 22 24 26 
Rated Current 
for Constant 
Torque (A) 
5  7.5 11 17 25 33 49 65 75 90 120 146 
Rated Current 
for Variable 
Torque (A) 
6.3  9.4 13.8
21.3
31.3
41.3
61.3
81.3 93.8
113 150 183 
Max. Carrier 
Frequency 
15kHz 9kHz 
 
460V Series 
kW 0.75 
1.5 
2.2 
3.7
5.5
7.5
11
15
18.5 
22 
30
37 
45 
55 
75 
HP 1.0 
2.0 
3.0 
5.0
7.5
10 
15
20
25 
30 
40
50 
60 
75 
100
Pr.00-00 
5  7  9  11 13 15 17
19
21 23 25
27 29 31  33 
Rated Current 
for Constant 
Torque (A) 
3 4.2 6 8.5
13 18 24
32
38 45 60
73 91 110
150
Rated Current 
for Variable 
Torque (A) 
3.8 5.3 7.5 10.6 16.3 22.5
30
40
47.5 56.3 75
91.3 113.8  138
188
Max. Carrier 
Frequency 
15kHz 9kHz 
6kHz