Delta Electronics DVP-SC Prospecto

Descargar
Página de 2
 
 
 
Warning
 
 
This Instruction Sheet only provides descriptions for electrical specifications, general specifications, installation & 
wiring. Other detail infromation about programming and intructions is compatible with SA/SX/SC series; please see 
PLC Application Manual. For more information about the optional peripherals, please see individual product 
instuction shee or “DVP-PLC Application Manual: Special module”. 
 
This is an OPEN TYPE PLC. The PLC should be kept in an enclosure away from airborne dust, humidity, electric 
shock risk and vibration. Also, it is equipped with protective methods such as some special tools or keys to open the 
enclosure, in order to prevent hazard to users or damage the PLC.. 
 
Do NOT connect the AC main circuit power supply to any of the input/output terminals, or it may damage the PLC. 
Check all the wiring prior to power up. To prevent any electromagnetic noise, make sure the PLC is properly 
grounded 
. DO NOT touch terminals when power on. 
 Introduction 
Thank you for choosing DELTA’s PLC DVP series. The DVP-SC series has a 12-points (8 input points + 4 
outputs) MPU with powerful instructions (the same instruction sets as SA/SX/SC series) for use. It also has an 
8K Steps program memory and high-speed pulse inputs(X10 and X11)/outputs (Y10 and Y11). For high-speed 
pulse, total bandwidth can up to 130KHz and 100KHz maximum for single input/output. Besides, it also 
provides instructions of position control and zero point return to use with high-speed pulse output. It could 
connect all extension units of DVP-SS series for various applications. 
 Product Profile and Outline 
 
Unit: mm 
Battery replacement: Battery replacement must be finished within 3 minutes, or the internal data of the PLC 
(including the program area, RTC and latched registers) could be lost or destroyed. 
 
1  Status indicators of POWER, RUN and ERROR 
12  Extension port for wire to connect extension module/unit 
2  RUN/STOP switch 
13  Mounting hole 
3  VR0: Start-up by M1178/D1178 Corresponding value  14  DIN rail track (35mm) 
4  VR1: Start-up by M1179/D1179 Corresponding value  15  Extension unit clip 
5  DIN rail clip 
16  RS-485 communication port (Master/Slave) 
6  I/O terminals 
17  DC Power input   
7  I/O point indicators 
18  2 pin removable terminal (standard accessory) 
8  COM1 (RS-232) (Rx) indicator 
19  Power input cable (standard accessory) 
9  COM2 (RS-485) (Tx) indicator 
20  Battery cover 
10  COM1 (RS-232) port 
21  Battery socket connection 
11  Nameplate 
22  Battery holder 
ENGLISH 
 Specifications 
 
   
Model 
    Item 
DVP12SC11T 
Power supply voltage 
MPU: 24V DC (-15% ~ +20%) (With DC input reverse polarity protection), 
Fuse 
2A/250V AC 
Power consumption 
4W MAX 
Insulation resistance 
5 M
Ω  and above at 500V DC (Between all inputs/outputs and earth) 
Noise immunity 
ESD: 8KV Air Discharge 
EFT: Power Line: 2KV, Digital I/O: 1KV, Analog & Communication I/O: 250V 
Damped-Oscillatory Wave: Power Line: 1KV, Digital I/O: 1KV 
RS: 26MHz ~ 1GHz, 10V/m 
Grounding 
The diameter of grounding wire cannot be smaller than the wire diameter of terminals L 
and N (All DVP units should be grounded directly to the ground pole). 
Environment 
Operation: 0°C ~ 55°C (temperature), 50 ~ 95% (humidity), pollution degree 2;   
Storage: -25°C ~ 70°C (temperature), 5 ~ 95% (humidity) 
Vibration/shock resistance 
Standard: IEC61131-2, IEC 68-2-6 (TEST Fc)/IEC61131-2 & IEC 68-2-27 (TEST Ea) 
Weight (approx. g) 
158 
Certificates 
 
 
 
 
Input Point Electrical Specification 
Input type 
DC (SINK or SOURCE) 
Input current 
24V DC 5mA 
Off → On, 
X0, X1, 18.5V DC and above 
X2 ~ X5, 16.5V DC and above 
X10, X11, 18.5V DC and above 
Active level 
On → Off, 
X0 ~ X5, X10, X11, below 8 V DC 
Hardware 
The constant of filter time is 10ms 
X0~X5 
Software 
0 ~ 20ms (Set by D1020) 
Hardware 
The constant of filter time is 4.7us   
 
Response time 
X10, X11 
Software 
0 ~ 1,000 times (Set by D1021) 
 
 
Output Specifications 
Output type 
Transistor 
0.3A/1 point @ 40°C (Room Temp.) 
Rated current 
When the output of Y0 and Y1 is high-speed pulse above 3KHz, Y0, Y1 ,Y10 and Y11 = 30mA 
Voltage specification 
5 ~ 30V DC 
Max. inductive load 
7.2W/24V 
Internal 
None 
Output protection 
Outside 
Rated value according to the load 
Y0, Y1 
9W/1 point 
Maximum loading 
Y10, Y11 
0.9W/1 point 
Off → On 
< 20us 
< 1us (Y10, Y11 only) 
Response time 
On → Off 
< 30us 
< 1us (Y10, Y11 only) 
Battery life: 
Temperature (
°C) 
25 
50 
70 
Life (years) 
Precision of calendar timer: 
At 0
°
C/32
°
F, less than -117 seconds error per month.   
At 25
°
C/77
°
F, less than 52 seconds error per month. 
At 55
°
C/131
°
F, less than -132 seconds error per month 
 Model Name & I/O Configuration 
Input/Output Specification 
Input Unit 
Output Unit 
Model 
Power 
Points 
Type 
Points 
Type 
I/O Configuration 
24V DC 
Sink/Source 
X0~X5 
Transistor 
Y0, Y1 
DVP12SC11T  24V DC 
24VDC 
Sink/Source 
Hi-speed 
X10, X11 
Transistor 
Hi-speed 
  Y10, Y11 
S/S
X0
X1
X2
X3
X4
X5
X10
X11
C0
Y0
C1
Y1
C2
Y10
C3
Y11
 
 Installation & Wiring 
4.1 PLC Mounting Arrangements and Wiring Notes   
1.  When installing the DVP series PLC, make sure that it is installed in an 
enclosure with sufficient space (as shown on the right) to its 
surroundings so as to allow heat dissipation.   
2.  I/O signal wires or power supply should not run through the same 
multi-wire cable or conduit.   
DV P
M P U
D
D
D
D
D > 50 mm
 
3.  Please use 22-16AWG (1.5mm) wiring (either single or multiple core) 
for I/O wiring terminals. The specification for the terminals is as shown 
on the right.     
4.  PLC terminal screws should be tightened to a torque of 1.95 kg-cm (1.7 
in-lbs). 
5.  Use copper conductor only, 60/75
°
22 -1 6AW G
< 1.5m m
 
4.2 Wiring Notes 
 Environment 
1.  DO NOT store the PLC in an atmosphere that is dusty, smoky, with metallic debris or corrosive or 
flammable gases. 
2.  DO NOT store the PLC in an environment with high temperature or high humidity. 
3.  DO NOT install the PLC on a shelf or on an unstable surface. 
 Power Input Wiring 
DVP-SC series input power supply is DC input. Please take a note of listed items when operating DVP-SC 
Series. 
1.  Please make sure the power is at terminals 24V DC and 0V (power range is 20.4 ~ 28.8V DC). When 
voltage is lower than 20.4V DC, PLC will stop operating, all outputs will be Off and ERROR LED will flash 
continuously. 
2.  If the power-cut time is less than 10ms, the PLC still operates unaffectedly. If the power-cut time is too 
long or the power voltage drops, the PLC will stop operating and all the outputs will be Off. Once the 
power is restored, the PLC will return to operation automatically. (There are latched auxiliary relays and 
registers inside of the PLC, please be aware when programming.) 
DC Input Type 
24V
2A
S/S
X0
X1
X2
20.4V~28.8V
0V
DC/DC
5V
 
 Safety Wiring
 
Since the PLC is used to control numerous devices, motion of either one device could affect the motion of other 
devices. Therefore the breakdown of a device would consequently be detrimental to the whole auto control 
system, thus the result is dangerous. Please use the recommended wiring below for the power input 
(DVPPS01/DVPPS02): 
  Power supply for AC loads 
  Power Circuit Protection Fuse (3A) 
  Power indicator 
 
Emergency stop 
The machinery must provide a quick manual method 
disconnecting all system power. 
 
Circuit isolation device (System Power Disconnect) 
Utilize the electromagnetic contactor and the relay to be the 
isolation unit of the power circuit to prevent the possible instability 
of the system when the power is supplied on and off.   
  DVPPS01/DVPPS02 
  Earth 
M C
MC
N
L
1
1
2
3
4
5
6
7
8
G u ar d
L im it
MC
 
 
Power supply: 
AC: 100 ~ 240V AC, 50/60Hz 
 Input Point Wiring
 
The DC power is used for DC input signal. Two types of DC wiring are used: SINK and SOURCE, defined as 
follows: 
Sink = Current flows into the common terminal S/S 
Source = Current flows out of common terminal S/S 
Sinking
S/S
X0
 
Sou rcin g
S/ S
X0
 
 
Input Point Loop Equivalent Circuit 
Wiring Loop 
DC Type 
  (DC Signal IN)   
SINK Mode 
+2 4V
24 G
S/S
X0
24V D C
S I NK
+ 5V
 
+24V
OV
Sink  Ty pe
X1
X2
S/S
X0
24 VD C
 
 
 
Input Point Loop Equivalent Circuit 
Wiring Loop 
DC Type 
  (DC Signal IN)   
SOURCE Mode 
+ 24 V
24 G
S/S
X0
24 V D C
S OU R C E
+ 5 V
 
Source Type
X1
X2
S/S
X0
+24V
OV
24VD C
 
 Output Point Wiring
 
DVP-**-**-11-T
TRANSISTOR  OUTPUT
LED
Y0
C0
LOAD
<  0.3A
T
R
G
 
1.  Two types of DVP-SC Series PLC output modules Transistor.    For the electrical specification, please refer 
to the function specification. 
2.  Please watch out the connection of common terminals while wire the outputs. Output terminal Y0 uses one 
common terminal C0, Y1 uses C1, and Y10 uses C2, Y11 uses C3, as shown below: 
C0 Y0 C1 Y1 C2 Y10 C3 Y11
 
Action indication: When the output point is active, the corresponding indicator at the front panel will be on. 
3.  Isolated circuit: The optical coupler is used to isolate signals between PLC internal circuits and input 
modules. 
 Input/Output Wiring
 
24V DC
S/ S
X0
X1
X5
X1 0
X11
Y0
C0
Y1
C1
Y1 0
C2
C3
Y11
LOAD
CH 0
CH 1
100KHz
100KHz
100K Hz
100K Hz
30 mA~0.3 A
5 VD C~ 30 V DC
High-speed pulse 
in put s
High-speed pulse 
in put s
X10 and X11 can be used as common inputs 
or inputs of high-speed counter
High-speed pulse 
outp uts
High-speed pulse 
outp uts
Y10 and Y11 can be used as common outputs or 
high-speed pulse outpus used with position control 
 
 
注意事項 
 
本使用說明書僅提供電氣規格、功能規格、安裝配線部份說明,其它詳細之程式設計及指令與
SA/SX/SC
系列
相容,詳細說明請見
DVP-PLC
應用技術手冊【程式篇】,選購之週邊裝置詳細說明請見該產品隨機手冊或
DVP-PLC
應用技術手冊【特殊模組篇】。
 
 
本機為開放型
(OPEN TYPE)
機殼,因此使用者使用本機時,必須將之安裝於具防塵、防潮及免於電擊
/
衝擊意
外之外殼配線箱內。另必須具備保護措施(如:特殊之工具或鑰匙才可打開)防止非維護人員操作或意外衝
擊本體,造成危險及損壞。
 
 
交流輸入電源不可連接於輸入/出信號端,否則可能造成嚴重損壞,請在上電之前再次確認電源配線。請勿
在上電時觸摸任何端子。本體上之接地端子
 
 
務必正確的接地,可提高產品抗雜訊能力。
 
  產品簡介 
DVP-SC
系列為一
12
點(
8
輸入點
  + 4
輸出點)
PLC
主機,除提供豐富的指令集(與
SA/SX/SC
指令集相同)、
8K Steps
的程式記憶體並具有高速脈波輸入
(X10
X11)
及輸出
(Y10
Y11)
,總和頻寬可達
130KHz
,單一輸入或
輸出最高可達
100KHz
。另外配合高速脈波輸出功能,提供定位控制及原點復歸指令。可連接
SS
系列全系列擴充
機,滿足各種應用場合。
 
 
產品外觀及各部介紹 
 
尺寸單位:
mm 
電池安裝
電池安裝
電池安裝
電池安裝:
:更換電池時,請在 3 分鐘內完成,否則 PLC 內部資料(包含程式區,萬年曆及停電保持暫存器)有可
能會消失或被破壞。
 
 
電源、運行及錯誤指示燈 
12 
擴充機連接口 
RUN
/STOP 開關 
13 
擴充機定位孔 
VR0
:M1178 啟動/D1178 對應值 
14 
DIN
軌糟  (35mm) 
VR1
:M1179 啟動/D1179 對應值 
15 
擴充機固定扣 
DIN
軌固定扣 
16 
RS-485
通訊口  (Master/Slave) 
輸出/入端子 
17 
電源輸入口 
輸出/入點指示燈 
18 
2 pin
脫落式端子(標準附件) 
RS-232
通訊接收  (Rx)  指示燈 
19 
電源輸入連接線(標準附件) 
RS-485
通訊傳送  (Tx)  指示燈 
20 
電池蓋 
10 
RS-232
程式輸出/入通訊口 
21 
電池插座連接 
11 
銘牌 
22 
電池座 
繁體中文
繁體中文
繁體中文
繁體中文    
  電氣規格 
 
 
 
機種   
 
項目 
DVP12SC11T 
電源電壓 
主機:24V DC (-15% ~ +20%)(具直流輸入電源極性反接保護) 
電源保險絲容量 
2A/250V AC 
消耗電力 
4W MAX 
絕緣阻抗 
5 M
Ω以上(所有輸出/入點對地之間 500V DC) 
雜訊免疫力 
ESD: 8KV Air Discharge 
EFT: Power Line: 2KV, Digital I/O: 1KV, Analog & Communication I/O: 250V 
Damped-Oscillatory Wave: Power Line: 1KV, Digital I/O: 1KV 
RS: 26MHz ~ 1GHz, 10V/m 
接地 
接地配線之線徑不得小於電源端 L, N 之線徑(多台 PLC 同時使用時,請務必單點接地) 
操作/儲存環境 
操作:0°C ~ 55°C(溫度),50 ~ 95%(濕度),污染等級 2 
儲存:-25°C ~ 70°C(溫度),5 ~ 95%(濕度) 
耐振動/衝擊   
國際標準規範 IEC61131-2, IEC 68-2-6 (TEST Fc)/IEC61131-2 & IEC 68-2-27 (TEST Ea) 
重量(約, g) 
158 (g) 
 
輸入點電氣規格 
輸入形式 
直流(SINK 或 SOURCE) 
輸入電流 
24V DC 5mA
約 10 ms 
Off → On, 
X0
、X1 為 18.5V DC 以上 
X2 ~ X5
為 16.5V DC 以上 
X10
、X11 為 18.5V DC 以上 
動作位準 
On → Off, 
X0 ~ X5
、X10、X11 為 8V DC 以下 
硬體 
濾波時間常數  10 ms 
一般輸入 
X0 ~ X5 
軟體 
由 D1020 可作 0 ~ 20 ms 的調整 
硬體 
濾波時間常數  4.7us 
反應時間 
高速輸入 
X10
、X11 
軟體 
由 D1021 作 0 ~ 1,000 次的調整 
 
輸出點電氣規格 
輸出點形式 
電晶體 
0.3A/1
點@ 40°C 
高速脈波輸出 3KHz 以上時 
電流規格 
Y0
、Y1 及 Y10、Y11 為 30mA 
電壓規格 
30V DC 
一般輸出  9W/1 點 
最大負載 
高速輸出  0.9W/1 點 
一般輸出  Off→On 20us, On→Off 30us 
反應時間 
高速輸出  Off→On 1us, On→Off 1us 
電池壽命
電池壽命
電池壽命
電池壽命:
 
溫度  (°C) 
25 
50 
70 
壽命  (年) 
萬年曆的精度
萬年曆的精度
萬年曆的精度
萬年曆的精度(
(秒
秒):
):
):
):
 
0
°
C/32
°
F
時,每月最大誤差
  -117
秒。
 
25
°
C/77
°
F
時,每月最大誤差
52
秒。
 
55
°
C/131
°
F
時,每月最大誤差
  -132
秒。