DVP-01HC 
High-speed Counter 
Module 
Instruction Sheet 
 
1  
WARNING 
 
  Please carefully read this instruction thoroughly prior to use the DVP-01HC. 
  Make sure that power is OFF before wiring.   
  This is an OPEN TYPE PLC. The PLC should be kept in an enclosure away from airborne 
dust, humidity, electric shock risk and vibration. Also, it is equipped with protective methods 
such as some special tools or keys to open the enclosure, in order to prevent hazard to users 
or damage the PLC.   
  Do NOT connect the AC main circuit power supply to any of the input/output terminals, or it 
may damage the PLC. Check all the wiring prior to power up.   
 
2   
INTRODUCTION 
 
2.1 
Model Name Explanation and Peripherals 
 
Thank you for choosing DELTA’s PLC DVP series. DVP-01HC high-speed counter input 
module could accept 200KHz pulse from external counter. It uses instruction FROM/TO to 
read/write the data in module via EH MPU. There are 33 Controlled Registers (CR, each 
register is 16-bit)
 
in each module. 32 bits data consists of two continuous CRs and allow 
executing itself after setting CR.   
 
The different counter modes, such as single-phase mode, two phases mode, 16-bit mode or 
32-bit mode, can be designated by CR. The controlled registers are written by instruction TO 
via MPU. When wiring, connect 24V, A24+, B24+, P24+, D24+, A12+, B12+, A5+, B5+, P5+ 
and D5+ to positive potential. In the same way, 0V, A24-, B24-, P24-, D24-, A12-, B12-, A5-, 
B5-, P5- and D5- should be connected to negative potential.   
 
Input signal source could be 1-phase or 2-phase encoder and voltage level could be 5V, 12V 
and 24V. Besides, it also provides two terminals, PRESET and DISABLE. When terminal 
“PRE” is on, the data in CR#10 and CR#11 will be sent to CR#20 and CR#21. That also means 
current value of counter will be changed to be factory setting. When terminal “DIS” is on, 
“count” operation is disabled.   
 
There are two outputs, YH0 and YH1, in hardware input module of DVP-01HC. When counter 
value is equal to the setting, the corresponding output point will activate. The transistors of 
output points are independent and isolated. 
 
Nameplate Explanation 
24VDC 3W MAX.
0.5 A  5VDC~30VDC  1~10KHz
01HC-H0T4350001
VX.XX
5VDC 12VDC  24
   1~200KHz
VDC
Input power supply spec.
Output module spec.
Barcode, serial number and version
Model Name
Input spec.
 
 
Model and Serial Number Explanation 
Serial Number
Model
for EH series MPU 
Product Series
Channel number 
Model type
Production series
Production week
Production year (2004)
Production place (Taoyuan)
Serial number of version
Production Model
序號
HC: High-speed counter module
 
2.2 
Product Profile and Outline 
1
2
3
4
7
7
5
3
6
10
8
9
 
Unit: mm 
1. DIN rail track (35mm) 
2. Mounting wire to connect extension module/extension unit
3. Model name 
4. Status Indicator (Power, Run and ERROR) 
5. DIN rail clip 
6. Terminal 
7. Mounting hole 
8. Terminal layout 
9. Extension port to connect extension module/unit 10. RS-485 communication port 
 
 
LED Display 
1.  Power   
: Power LED. When external +24V power is applied, it will be ON. 
2.  L.V. 
: Low voltage LED. When external power supply is lower than 19V, it will be ON. 
3.  UP   
: Count up LED 
4.  DOWN   
: Count down LED 
5.  ψA   
: When input point A is ON, it will light. 
6.  ψB   
: When input point B is ON, it will light. 
7.  PRE 
: PRESET LED. When external terminal PRE is ON, it will light.   
8.  DIS   
: DISABLE LED. When external terminal DIS is ON, it will light. 
9.  YH0, YH1    : When output points YH0 and YH1 are ON, it will light. 
2.3
 
Wiring
 
To suit M3.5 screw terminals
Below 6.2
Below 6.2
1. Please use O-type or Y-type terminals for I/O wiring terminals. The 
specification for the terminals is as shown on the left. Tighten PLC 
terminal screws to a torque of 5 to 8 kg-cm (4.3~6.9 in-lbs).   
2. I/O signal wires or power supply should not run through the same 
multi-wire cable or conduit.   
3.  Use copper conductor only, 60℃.  
 
External Wiring 
4.7K
Shielded wire
A24+
OA
A12+
A5+
A -
B24+
B12+
B5+
B -
2.2K
0.68K
4.7K
2.2K
0.68K
P+24
P+5
PRE-
D+24
D+5
DIS-
4.7K
4.7K
0.68K
4.7K
4.7K
0.68K
OB
PRESET
DISABLE
START
EH MPU
connection 
wire
YH0+
YH0-
YH1+
YH1-
+24V
0V
Filter
DC/DC
+24V
+5V
0V
+24V
External Power
DC 12V to 24V
01HC High-speed Counter Module
OUT
OUT
OUT
A phase
B phase
Z phase
+24V
COME
0V
+24V
External Power
DC5V, 12V, 24V
PNP  output encoder
Shielded wire
Shielded wire
Shielded wire
 
Make sure the positive/negative pole of 01HC input terminal wiring is correct when using NPN 
encoder.  
 
Start-up current for 01HC is I
PEAK
=0.8A and general working current is I
MAX
=0.2A(input voltage 
is +24V).
 
 
3
FUNCTION SPECIFICATION
 
3.1 Function 
Specification 
1-phase Input 
2-phase (A, B) Input 
Item 
1 Input 
2 Inputs 
Normal 
Frequency 
Double 
Frequency 
Four Times 
Frequency 
Power Supply 
DC24V(-15% ~ +20%), Current consumption 140±30mA 
Power is supplied from PLC or external power supply. 
Max. Number of Connecting 
Units 
8 units; (All I/O points are not occupied. There can be 8 special extension units at 
most connected to EH series.) 
Voltage 
Level 
Terminals [A24+], [B24+]: DC24V  ±10 % 
Terminals P24+], [D24+]: DC12V ~24V  ±10 % 
Terminals [A12+], [B12+]: DC12V  ±10 % 
Terminals [A5+], [B5+], [P5+], [D5+]: DC5V  ±10 % 
Choose only one suitable voltage level for positive   
pole of each signal.   
A: A Phase 
B: B Phase 
P: Preset 
D: Disable 
Max. Count 
Frequency 
200KHz 200KHz 200KHz 100KHz  50KHz 
Input 
Signal 
Waveform 
t
3
t
1
t
1
t
2
t
2
t
3
t1: rise/fall time≦0.8us 
t2: On/Off pulse width≧2.5us 
t3: phase difference between A phase and B 
phase  ≧1us 
PRESET input: input pulse width≧50us 
DISABLE input: input pulse width≧50us 
Count Mode 
There is three count modes: count up/down ((2-phase input for AB phase), 
1-phase 2 inputs and 1-phase 1 input.) 
Range 
32-bit mode: -2,147,483648~+2,147,483,647 
16-bit mode: 0~65,536 (upper limit can be set by CR#2,3) 
Count 
Specification 
Comparison 
Method 
Two comparison values are available and correspond to two outputs, YH0 and 
YH1, respectively. When count value is equal to settings, the output will be ON. It 
adopts hardware circuit comparison and output settings with real-time handle.   
Output 
Form 
YH0+: output point YH0, transistor: Collector 
YH0-: output point YH0, transistor: Emitter 
YH1+: output point YH1, transistor: Collector 
YH1-: output point YH1, transistor: Emitter 
YH0+
YH1+
YH1-
YH0-
 
Output 
Signal 
Output 
5V TO 30VDC, 0.5A 
Connect to DVP-PLC 
MPU in Series 
The module number it connects to MPU from closest to the farthest is from 0 to 
7. 8 modules is the max and it won’t occupy any digital I/O.   
3.2 Other 
Specification
 
Environmental specifications 
Operation/Storage 
1. Operation: 0℃~55℃(Temperature), 50~95%(Humidity), pollution degree 2 
2. Storage: -25℃~70℃(Temperature), 5~95% (Humidity) 
Vibration/Shock 
immunity 
Standard: IEC1131-2, IEC 68-2-6 (TEST Fc) / IEC1131-2 & IEC 68-2-27 (TEST 
Ea) 
Antistatic spec. 
All places between terminals and ground comply with the spec. 
 
4
CONTROLLED REGISTER (CR) 
 
DVP-01HC High-speed Counter Module 
CR No. 
HW LW
Communi
cati
on 
Address 
Latched 
Attr
ibute 
Content 
Setting Range 
#0 H415E 
 
Model type 
System used, read only, DVP-01HC model code=H’0120 
#1 H 415F  ╳ R/W 
Count 
up/down mode 
setting 
Setting range: 0-1, factory setting K0 
1-phase 1 input(Software): count up/down mode setting, 
count up: K0, count down:K1 
#3 #2 H 4160  ╳ R/W  Ring length 
16-bit: factory setting is K65,536. 
 
Example: 
M0
DTO
K0
K2
K200
K1
 
Write K200 into first extension module CR#2 and 
CR#3 (i.e. CR#3 = 0, CR #2 = 200). Setting 
range: K2 to K65,536. 
198
199
1
0
0
1
199
198
Count up
Count down
When ring length is set to K200, The count value 
will be as shown on the left. 
Count up: when count value reaches 199, the 
next count value will be 0. 
Count down: when count value reaches 0, the 
next count value will be 199. 
Setting notices: 
1.  It must write with 32-bit.   
2.  It only can be write-in when writing value is greater or equal to current count value. 
3.  It only can be set when counter stops counting and count mode is 16-bit.