Delta Electronics DTE-2DS Prospecto

Descargar
Página de 2
 Parameter 
 and 
  can be set up when parameter 
  is set as “0”. 
 
can be set up when 
  is not “0”. 
 Parameter 
 and 
  (control cycle for output 1) can be set up when parameter 
  is set as 
 (heating) or 
 (cooling) output. 
  (control cycle for output 2) 
can be set up when parameter 
  is set as 
 (heating) or 
 (cooling) output. 
 Parameter 
 and 
Can be set up when parameter 
 and 
  are set as 
 (heating) or 
  (cooling) output. (The settings in 
 and 
  have to be 
different.) 
For ON/OFF Control Application: 
1.  Set up 2 outputs: Enter parameter 
 and 
  in “initial setting mode” (see “Setting up 
Parameters” section for details). Set up one of the two parameters as 
 or 
 of control 
output. 
2.  Set up control type: Enter parameter 
  in “initial setting mode” (see “Setting up Parameters” 
section for details) and set it up as 
 (ON/OFF) control. 
3. Set up parameters: In “regulation mode” 
 Parameters 
 and 
  (hysteresis for output 1) can be set up when parameter 
  is set as 
 (heating) 
 (cooling) output. 
  (hysteresis for output 2) can be 
set up when parameter 
  is set as 
 (heating) or 
  (cooling) output. You can 
only set up 
 when 
 and 
  are set as 
 or 
  at the same time. 
 Parameter 
Can be set up when parameter 
 and 
  are set as control output, 
and the settings in 
 and 
  are different, e.g. output 1 is 
  (heating), and output 
2 is 
 (cooling). 
For Manual Control Application: 
1.  Set up 2 outputs: Enter parameter 
 and 
  in “initial setting mode” (see “Setting up 
Parameters” section for details). Set up one of the two parameters as 
 or 
 of control 
output. 
2.  Set up control type: Enter parameter 
  in “initial setting mode” (see “Setting up Parameters” 
section for details) and set it up as 
 (manual) control. 
3. Set up parameters: In “regulation mode” 
 Parameter 
 and 
  (control cycle for output 1) can be set up when parameter 
  is set as 
 (heating) or 
 (cooling) output. 
  (control cycle for output 2) 
can be set up when parameter 
  is set as 
 (heating) or 
 (cooling) output. 
 Parameter 
 and 
  (in “operation mode”):
  can be set up when parameter 
  is set as 
 (heating) or 
 (cooling) output. 
  can be set up when 
parameter 
 is set as 
 (heating) or 
 (cooling) output. 
For Programmable PID Application: 
1.  Set up 2 outputs: Enter parameter 
 and 
  in “initial setting mode” (see “Setting up 
Parameters” section for details). Set up one of the two parameters as 
 or 
 of control 
output. 
2.  Set up control type: Enter parameter 
  in “initial setting mode” (see “Setting up Parameters” 
section for details) and set it up as 
 (programmable) control. 
3. Set up parameters: In “regulation mode” 
 Parameter 
 , 
 and 
 . 
 Parameter 
  can be set up when parameter 
  is set as “0”. 
 Parameter 
 and 
  (control cycle for output 1) can be set up when parameter 
  is set as 
 (heating) or 
 (cooling) output. 
  (control cycle for output 2) 
can be set up when parameter 
  is set as 
 (heating) or 
 (cooling) output. 
 Parameter 
 and 
Can be set up when parameter 
 and 
  are set as 
 (heating) or 
  (cooling) output. (The settings in 
 and 
  have to be 
different.) 
 Parameter 
 and 
  (in “operation mode"):Can be set up when parameter 
 is 
set as 
 or 
  . 
For Proportional Output Application: In this application, output 1 has to be analog output. 
1.  Set up output function: Enter parameter 
  in “initial setting mode” (see “Setting up Parameters” 
section for details) and set it as 
 (proportional) output. 
2. Set 
up 
parameters: In “regulation mode” 
 Parameter 
 
For Upper/Lower Limits of Control Output: 
1.  Set up upper limit: Enter parameter 
  in “regulation mode” (see “Setting up Parameters” 
section for details). Range: Lower limit ~ 100%. 
2.  Set up lower limit: Enter parameter 
  in “regulation mode” (see “Setting up Parameters” 
section for details). Range: 0 ~ upper limit %. 
For Alarm Application: 
1.  Set up output function (only when there is group INB): Enter parameter 
  in “initial setting 
mode” (see “Setting up Parameters” section for details) and set it as 
 (alarm) output. 
2.  Set up alarm type: Enter parameter 
  (with INB) or 
 and 
 (without INB) in “initial 
setting mode”. See Table 2 for more details on the alarm output. 
3. Set up parameters: In “operation mode” 
 Parameter 
 and 
Can be set up when there is group INB. 
 Parameter 
 , 
 , 
 and 
Can be set up when there is no group INB. 
4.  Set up delay alarm output: Enter parameter 
  in “regulation mode” (unit: second). The alarm 
will be enabled only when the temperature reaches the alarm output condition, and the condition 
remains until the delay time is reached. 
DTE main unit offers 2 groups of alarm output, each with 12 alarm modes in the initial setting mode. 
When SV is higher or lower than SV, the alarm output will be enabled. See the table in the next column 
for the explanations on the 12 alarm output modes.   
Note: AL-H and AL-L include AL1H, AL2H and AL1L, AL2L.
 
SV 
Alarm Mode 
Alarm Output Operation 
0 No 
alarm 
OFF 
Alarm output is enabled when the temperature reaches upper 
and lower limits: The alarm will be enabled when PV exceeds 
SV + AL-H or falls below SV – A L-L. 
ON
OFF
AL-L
SV
AL-H
 
Alarm output will be enabled when the temperature reaches the 
upper limit: The alarm will be enabled when PV exceeds SV + 
AL-H. 
ON
OFF
SV
AL-H
 
Alarm output will be enabled when the temperature reaches the 
lower limit: The alarm will be enabled when PV falls below SV – 
A L-L. 
ON
OFF
AL-L
SV
 
Alarm output will be enabled when PV is between SV + AL-H 
and SV – AL-L.   
ON
OFF
AL-L
SV
AL-H
 
Alarm output will be enabled when the temperature reaches the 
absolute value of the upper and lower limits: The alarm will be 
enabled when PV exceeds AL-H or falls below AL-L. 
ON
OFF
AL-L
AL-H
 
Alarm output will be enabled when the temperature reaches the 
absolute value of the upper limit: The alarm will be enabled 
when PV exceeds AL-H. 
ON
OFF
AL-H
 
Alarm output will be enabled when the temperature reaches the 
absolute value of the lower limit: The alarm will be enabled when 
PV falls below AL-L. 
ON
OFF
AL-L
 
Upper/lower limit standby alarm: The alarm will be enabled when 
PV reaches SV and further exceeds SV + AL-H or falls below 
SV – AL –L. 
ON
OFF
AL-L
AL-H
SV
 
Upper limit standby alarm: The alarm will be enabled when PV 
reaches SV and further exceeds SV + AL-H. 
ON
OFF
SV
AL-H
 
10 
Lower limit standby alarm: The alarm will be enabled when PV 
reaches SV and further falls below SV – AL-L. 
ON
OFF
AL-L
SV
 
11 
Upper limit hysteresis alarm: The alarm will be enabled when PV 
exceeds SV + AL-H. The alarm will be disabled when PV falls 
below SV. 
ON
OFF
AL-L
SV
AL-H
 
12 
Lower limit hysteresis alarm: The alarm will be enabled when PV 
falls below SV – AL-L. The alarm will be disabled when PV 
exceeds SV. 
ON
OFF
AL-L
SV
AL-H
 
Table 2 
 Setting up Communication 
1. Set 
up 
communication: Enter parameter 
 , 
 , 
 , 
 , 
 and 
 
in “initial setting mode” (see “Setting up Parameters” section for details) and select your desired 
communication settings. 
2.  DTE series temperature controller is able to set up or read communication settings through 
DTE-2DS. 
 
 Selecting Channel 
1. Select 
channel: Enter parameter 
  in “regulation mode” (see “Setting up Parameters” section 
for details) and select the channel to be monitored. 
2.  How does it work: DTE main unit has maximum 8 channels which can be connected to 8 input 
sensors at the same time. The 8 input channels belong to group INA and INB, each group with 4 
input channels. INB is optional accessory; therefore if INB is not inserted in DTE, DTE will only 
show 4 channels.
 
 Setting up Copy Function 
1.  Set up the function: Enter parameter 
  in “initial setting mode” (see “Setting up Parameters” 
section for details) and select the function you desire. 
2.  How does it work: The copy function allows a DTE main unit to copy its parameters (including the 
values set in the parameter and communication settings) to another DTE main unit through 
DTE-2DS. Follow the steps below: 
a.  Insert DTE-2DS into the DTE main unit to be copied. Enter parameter 
  in “initial setting 
mode” and select 
, and DTE-2DS will read the parameters in the DTE main unit. Next, you 
will see 
  on the screen, indicating that the copy is successful. 
  indicates the copy 
fails. Press 
  to return to “operation mode” and you will see the present temperature value 
(PV) and set temperature value (SV). 
b. 
Switch off DTE and withdraw DTE-2DS. Insert DTE-2DS into another DTE main unit. Enter 
parameter 
  in “initial setting mode” and select 
  . DTE-2DS will write the 
parameters into it. Next, you will see 
  on the screen, indicating that the writing-in is 
successful. 
  indicates the writing-in fails. Press 
  to return to “operation mode” and 
you will see the present temperature value (PV) and set temperature value (SV).
 
 Locking the Keys on Panel 
1. Lock 
the 
keys: Enter parameter 
  in “operation mode” (see “Setting up Parameters” section 
for details) and select the function you desire. 
2.  How does it work: 
  indicates locking all the keys on the panel. 
  indicates that you can 
only modify the set temperature value (SV), and all other functions are locked. 
3. 
Press 
 and 
  at the same time to unlock the keys.
 
 Analog Output & Temperature Tuning 
1.  Set up analog output tuning: Enter parameter 
 and 
  in “regulation mode” (see 
“Setting up Parameters” section for details) and tune the parameter to the desired output value. 
2. Temperature 
offset 
tuning: Enter parameter 
  in “regulation mode” and tune the parameter to 
the displayed temperature value. 
3.  How does it work: 
a.  Tuning analog output: For example, if you would like to have accurate 4 ~ 20mA of output, you 
can set up output 0% by manual control, connect the output to ampere meter and tune 
parameter 
  making the meter point to 4mA. Next, set up output 100% by manual control 
and tune parameter 
  making the meter point to 20mA. 
b. 
Tuning temperature offset: This allows the displayed temperature to plus or minus 1 offset value.
 
 
Error Message 
Error 
PV 
SV 
Input sensor not connected 
 
 
Internal communication error 
 
 
Output error 
 
 
Input error 
 
 
Storage error 
 
 
Channel disabled 
 
 
Channel being initialized 
 
 
 How to Install 
1
 
Remove all the terminal blocks on the panel.
 
 
2
 
Uncover the panel and insert DTE-2DS to the 
“operation interface” slot.
 
 
3
 
Cover up the panel.
 
 
4
 
Insert the terminal blocks back to their 
positions.
 
 
 
The content of this instruction sheet may be revised without prior notice. Please consult our distributors or   
download the most updated version at http://www.delta.com.tw/industrialautomation