Eaton Electrical MN05001002E Manual De Usuario

Descargar
Página de 29
 
Intelligent Technologies QCPort System Install Manual 
November 2005  
 
MN05001002E 
For more information visit 
www.eatonelectrical.com
  
Page 
19
 
Table 3: RJ Interconnect Maximum Current 
QCPort Interconnect Cable 
Allowable Current 
10 [25] inch [cm] 
1.0 A 
3 [1] feet [meter] 
1.0 A 
6 [2] feet [meter] 
1.0 A 
10 [3] feet [meter] 
1.0 A 
 
The voltage range between +24 and G must be between 18 and 28V DC. 
Locating a Power Supply 
The QCPort interconnect system allows several options for supplying power, as outlined 
in this section. To determine which option meets your needs, consider the distribution of 
the loads, power supply location, and the number of power supplies used.  Power 
supplies must be 24 volts. 
 
Notice 
In the United States and Canada, the power supply must also be Class 2. 
 
 Warning 
Whenever two or more power supplies are connected to the same segment, the 
ground for the system must be referenced to only one point.