B.2 Hardware interface 
The hardware interface used to access the I-7000/8000/87K series I/O modules can be 
divided into the following: 
z  RS-232: I-8000 MCU with DCON_nnn.exe or 8K232.exe firmware. 
Baud Rate: 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200bps. 
Data format is: 1 start bit, 8 data bits, non-parity, 1 stop bit 
z  RS-485: I-7000/87K series I/O modules and I-8000 MCU with DCON_nnn.exe (or 
8K485.exe ) firmware   
Baud Rate: 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200bps. 
Data format is: 1 start bit, 8 data bits, non-parity, 1 stop bit 
z  Ethernet: I-8000E MCU with E10M_nnn.exe (or 8KE10.exe) firmware 
Speed: 10Mbps 
Even though the I-7000/87K series I/O modules are not equipped with an Ethernet interface, 
by using the I-7188E/8000E in connection with the VxComm technique, they can still    be 
accessed via the Ethernet. 
 
Note: 
1.  I-8000 MCU includes 8410, 8411, 8810, 8811, 8430,8431, 8830, 8831, 8KE4, 8KE8. 
2.  8000E means an I-8000 MCU equipped with an Ethernet port, such as 8430, 8431, 
8830, 8831, 8KE4, 8KE8. 
3.  Both the I-8000 and I-87K series I/O modules can be inserted into the I-8000 MCU 
simultaneously. 
4.  When the I-87K series I/O module is inserted into the I-8000 MCU, it uses the same 
commands as the I-8000 series I/O modules . 
5.  The 87K series expansion unit series includes 87K4, 87K5, 87K8, 87K9.  
6.  The I-87K series I/O modules use different commands when they are inserted into the 
I-8000 MCU and the I-87K expansion unit.
8430/8830/8KE4/8KE8 User’s manual, Jan 2005, Version 1.0, 8MS-002-10    -----    80