Cisco 7500 Series Installation and Configuration Guide
OL-5008-03 B0
Chapter 2      Preparing for Installation
  Environmental Monitoring and Reporting Overview for the Cisco 7500 Series
  +24 volts measured at  23.70(V)
  Airflow temperature measured at 35(C)
  Inlet   temperature measured at 26(C)
When the system power is on, all six fans in the fan array must be operational. If the system detects a 
failed or failing fan, it will display a warning message on the console screen. If the condition is not 
corrected within 2 minutes, the entire system will shut down to avoid an overtemperature condition and 
possible damage. 
The system uses a Hall Effect signal to monitor the six fans in the array. The current to the fans and the 
magnetic field generated by the fans’ rotation generate a voltage, which the system monitors to 
determine if all of the fans are operating. If the monitored voltage signal drops below a specified value, 
the system assumes a fan failure and initiates a system shutdown.
In the following example, the system has detected an out-of-tolerance fan, which it interprets as a fan 
failure. The failure message is displayed for 2 minutes before the system shuts down.
%ENVM-2-FAN: Fan array has failed, shutdown in 2 minutes
If the system does shut down because of a fan failure, the system will display the following message on 
the console screen and in the environment display and in the show environment command display when 
the system restarts:
Queued messages:
%ENVM-1-SHUTDOWN: Environmental Monitor initiated shutdown
Cisco 7507 and Cisco 7507-MX Environmental show Command Examples
In the Cisco 7507 and Cisco 7507-MX, the show environment command display reports the current 
environmental status of the system. The report displays parameters that are out of the normal values. No 
parameters are displayed if the system status is normal. The example that follows shows the display for 
a system in which all monitored parameters are within normal status range. 
Router# show env
All measured values are normal
If the environmental status is not normal, the system reports the worst-case status level in the last line of 
the display. 
In the Cisco 7507 and Cisco 7507-MX, the show environment last command retrieves and displays the 
NVRAM log showing the reason for the last shutdown (if the shutdown was related to voltage or 
temperature) and the environmental status at that time. Air temperature is measured and displayed, and 
the DC voltages supplied by the power supply are also displayed. 
Following is sample output of the show env last command:
Router# show env last
RSP(2) Inlet       previously measured at 27C/80F
  RSP(2) Hotpoint    previously measured at 38C/100F
  RSP(2) Exhaust     previously measured at 31C/87F
  +12 Voltage        previously measured at 12.17
  +5 Voltage         previously measured at 5.19
  -12 Voltage        previously measured at -12.17
  +24 Voltage        previously measured at 23.40
In the Cisco 7507 and Cisco 7507-MX, the show environment table command displays the temperature 
and voltage thresholds for each of the three RSP temperature sensors for each monitored status level: 
low critical, low warning, high warning, and high critical, which are the same as those listed in