Chapter 2      Preparing for Installation
  Equipment Rack-Mounting Guidelines
Figure 2-9
Airflow Through the Cisco 7513, Cisco 7513-MX, and Cisco 7576
The power supplies have their own fans with airflow that is independent of the chassis airflow. Ensure 
that there is minimum front and back clearance of 6 inches (15.24 cm).
Equipment Rack-Mounting Guidelines
This section provides the equipment rack-mounting guidelines that must be observed before installing a 
Cisco 7500 series router in an equipment rack. 
General Equipment Rack Ventilation Considerations
If you plan to install the router in an equipment rack, you can avoid overtemperature conditions by 
observing the following precautions: 
There must be at least 2 inches (5.08 cm) of clearance between each side of the chassis and the side 
(or inner wall) of an enclosed rack.
Enclosed racks must have adequate ventilation or an exhaust fan; use an open rack whenever 
possible.
A ventilation system that is too powerful in a closed rack can also prevent cooling by creating 
negative pressure around the chassis and redirecting the air away from the inlet vents. If necessary, 
operate the chassis with the rack open.
The correct use of baffles in an enclosed rack can help to ensure that cool air reaches the chassis. 
Power supplies
Card cage
System blower
H3093
Intake air
Exhaust air